Trouble Diagnosis

3. W-2WAY ECO-i Alarm Codes

E16 Alarm

Alarm code

E16

 

 

Alarm meaning

Automatic address setting alarm (too many units)

Alarm conditions

There were a number of indoor units was too many when Automatic address setting was performed

 

at a number of indoor units.

 

After initial communications were completed, an unrecognized unit was detected.

Probable cause

(1) The SW for setting the number of indoor units is incorrect.

 

(2)

The inter-unit control wiring is wired incorrectly.

 

 

Check

(1) Refer to the test run servicing materials and check the number of indoor units that is set.

 

(2)

Check the inter-unit control wiring at the indoor and outdoor units.

 

 

Correction

After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic

 

address setting again.

Example

 

Notes

 

E20 Alarm

 

 

 

 

Alarm code

E20

 

 

Alarm meaning

No indoor units at automatic address setting.

Alarm conditions

When automatic address setting was performed, no indoor units were recognized.

Probable cause

(1)

The inter-unit control wiring from the outdoor unit to the indoor units has been cut.

 

(2)

Serial connector (OC: CN001) is disconnected at the outdoor unit.

 

(3)

The power is OFF at all indoor units in the system.

Check

(1)

Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.

 

(2)

Check whether serial connector (OC: CN001) is disconnected at the outdoor unit.

 

(3)

Check the power at the indoor units.

Correction

(1)

Reconnect the inter-unit control wire from the outdoor unit to the indoor unit.

Example

 

Notes

Position of serial connector (OC: CN001) on W-2WAY control PCB

CN001

E24 Alarm

Alarm code

E24

 

 

Alarm meaning

Outdoor unit (main) failed to receive signal from other outdoor unit (sub).

Alarm conditions

After initial communications were completed, communications from an outdoor unit stopped.

Probable cause

(1) After initial communications were completed, the outdoor unit main/sub control wiring was cut.

 

(2) After initial communications were completed, the outdoor unit power was turned OFF.

Check

Correction

Example

Notes

 

 

3-7

1

2

3

4

5

6

7

8

Page 69
Image 69
Sanyo UHX3652, UHX2452 E16 Alarm Alarm code, At a number of indoor units, E20 Alarm Alarm code, E24 Alarm Alarm code