Service Checker

1. Outdoor Unit Maintenance Remote Controller

6. Setting the Outdoor Unit EEPROM Data

This function is used to make the outdoor unit

EEPROM data settings.

„ Setting mode 1

 

 

4

 

 

 

Press the

(CHECK) button and the

(VENTILATION) button simultaneously for 4 sec-

onds or longer.

 

 

 

Press the temperature setting

and

buttons to change the item code. The item codes

and setting data are shown in the table below.

Press the timer time

and

buttons to

change the setting data.

 

 

To confirm the changed setting data, press the (SET) button.

(At this time, the “SET DATA” display stops blinking and remains lit.)

” blinks when this mode is engaged, and

” appears in the outdoor unit address section. The item code number (values shown in the table below) and the corresponding setting data (6 dig- its) are also displayed. (The 6 digits of the setting data are displayed by changing between the first 3 digits (Fig. (A) and the last three digits (Fig. (B). When the first 3 digits are displayed, the top dot of the colon is illuminated.)

To exit setting mode, press the (CHECK) button.

(A)

1

3

2

(A) and (B) are displayed alternately.

(B)

1

2

3

Code

Parameter

 

Description (SET DATA)

 

No.

 

 

 

 

 

 

 

 

 

 

0000

= Sensor input not present. Control is performed.

 

 

Snowfall sensor usage

0001

= Sensor input present. Control is performed.

 

 

0002

= Sensor input not present. Control is not performed.

 

 

 

 

0003

= Sensor input present. Control is not performed.

 

 

 

 

 

 

 

 

Outdoor unit fan Quiet mode

0000

= Disabled

0001 = Quiet mode 1

 

 

0002 = Quiet mode 2

0003 = Quiet mode 3

 

 

 

0004

= Quiet mode 4

 

 

 

 

Cooling

0000

Heat pump

 

 

 

 

0001

Cooling

 

 

 

 

 

 

 

 

 

Demand 1 current

0000

= 0% 0001 = 40 ...

0004 = 70

0007 = 100

0008 = 120

 

0009

= 140 0010 = 160

0011 = 200

0012 = –1 (no limit)

 

 

 

Demand 2 current

0000

= 0% 0001 = 40 ...

0004 = 70

0007 = 100

0008 = 120

 

0009

= 140 0010 = 160

0011 = 200 0012 = –1 (no limit)

 

 

6-9

4

5

6

7

8

Page 111
Image 111
Sanyo UHX0752, UHX2452, UHX1252, UHX3652, UHX1852, THX2452, THX1252, THX1852 Code Parameter Description SET Data, „ Setting mode