PCB and Functions
1.Outdoor Unit Control PCB
2.Functions (for CR-CHDX14053)
Automatic address setting | 2P plug (white): Automatic address setting pin | |
(CN100) | • | |
| ||
|
| units that are connected to that outdoor unit and are within the same system. |
| • The system address is "1" at the time of shipment. Automatic address setting is necessary | |
|
| even for communications lines in a single system where the |
|
| not cross to any other systems. |
| • While automatic address setting is in progress, the 2 LEDs (LED1, 2: red) on the outdoor | |
|
| unit control PCB blink alternately. |
|
| in progress will stop the automatic address setting operation.) |
|
| |
S002 | Rotary switch (10 positions, black): Outdoor system address setting switch | |
| • The setting is "1" at the time of shipment. It is not necessary to change the setting if wiring | |
|
| is connected only to an outdoor unit and indoor units in a single system and the |
|
| control wiring does not cross multiple systems. |
| • | If wiring links the |
|
| lines, then a different address must be set for each refrigerant tubing system. |
| • | If wiring links multiple systems, a maximum of 30 systems (up to 64 indoor units) can be |
|
| connected. This setting can be set up to "39," however control will be for 30 systems even |
|
| if the setting is set to higher than 30. An alarm will be displayed if system addresses are |
|
| duplicated. (For details, refer to Table |
|
| |
S003 | DIP switch (2P, blue): Switches for setting system address 10s digit and 20s digit | |
| • | If 10 systems or more are set, the setting is made by a combination of this DIP switch and |
|
| S002. |
| • | If 10 - 19 systems are set, set switch 1 (10s digit) to ON. |
| • | If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to OFF. |
| • | If 30 systems are set, set both switch 1 (10s digit) and switch 2 (20s digit) to ON. (For |
|
| details concerning S002 and S003, refer to Table |
|
| |
S004 | Rotary switch (10 positions, red): Switch for setting the number of connected indoor units. In | |
| order to allow the outdoor unit to manage indoor units in the same refrigerant system, set the | |
| number of connected indoor units. (For details, refer to Table | |
|
| |
S005 | DIP switch (3P, blue): Switches for setting the 10s, 20s, and 30s digit for the number of | |
| connected indoor units | |
| • | If 10 systems or more are set, the setting is made by a combination of this DIP switch and |
|
| S004. |
| • | If 10 - 19 systems are set, set only switch 1 (10s digit) to ON. |
| • | If 20 - 29 systems are set, set switch 2 (20s digit) to ON, and set switch 1 (10s digit) to OFF. |
| • | If 30 - 39 systems are set, set only switch 3 (30s digit) to ON. (For details concerning S004 |
|
| and S005, refer to Table |
|
| |
S006 | DIP switch (3P, blue): Switch for setting the number of outdoor units | |
| • | Turn the switches ON according to the number of outdoor units (1 - 4). (For details, refer to |
|
| Table |
|
| |
S007 | DIP switch (3P, blue): Unit No. setting switch | |
| • The setting is "1" at the time of shipment. (For details, refer to Table | |
|
| |
S010 | DIP switch (3P, blue): Backup operation switch | |
| If an INV compressor has malfunctioned, turn CT1 ON and Back Up SW ON to operate the | |
| outdoor unit using only the | |
| If a | |
| operate the outdoor unit using only the INV compressor. (Disconnect the wiring from the | |
| ||
|
|
|