Trouble Diagnosis

3. W-2WAY ECO-i Alarm Codes

H31 Alarm

 

Alarm code

 

H31

 

 

 

 

 

 

 

 

 

Alarm meaning

 

HIC trouble alarm

 

 

 

Alarm conditions

 

This alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC

 

 

 

 

temperature or other trouble) from the HIC.

 

 

 

 

 

The HIC judges the current and temperature, and outputs the trouble signal. In general this

 

 

 

 

indicates trouble with the HIC itself.

 

 

 

 

 

 

 

 

Probable cause

 

Overcurrent in HIC circuit, and resultant abnormal heating, caused by HIC failure

 

 

 

 

 

 

 

Check

 

Check the power wiring and connector wiring. If the wiring and connectors are normal, use a

 

 

 

 

 

 

 

tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).

 

 

 

If there is a short circuit, there is an HIC malfunction.

 

 

 

 

 

HIC -

HIC +

 

HIC PCB

 

 

Correction

If an HIC failure is found, replace the PCB.

Example

Notes

Turn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.

L04 Alarm

 

 

 

Alarm code

L04

 

 

Alarm meaning

Outdoor unit refrigerant system address duplication

Alarm conditions

Communication by inter-unit control wiring was received that contained the same address as that

 

unit 5 times or more within 3 minutes.

Probable cause

Incorrect outdoor system address settings

Check

Check the system address settings again.

Correction

Correct the system address settings.

Example

Notes

Recovery from this alarm occurs automatically (when communication that contains the same

 

address as that unit is not received for 3 minutes after detection).

L05 Alarm

 

 

 

Alarm code

L05

 

 

Alarm meaning

Duplicated indoor unit priority (alarm at priority indoor units)

 

 

Alarm conditions

Multiple indoor units set as the priority unit were detected.

 

 

Probable cause

More than one indoor unit is set as the priority unit.

 

 

Check

From the wired remote controller, use the indoor unit EEPROM simple settings mode and

 

check whether or not the value for item code 04 is “0001.”

 

 

Correction

If the value of indoor unit EEPROM item code 04 is incorrect, set the correct value from the

 

wired remote controller.

Example

Notes

This alarm is displayed at the indoor units which are set as the priority unit. At indoor units which

 

are not set as the priority unit, alarm L06 is displayed.

 

3-16

Page 78
Image 78
Sanyo DHX3652, UHX2452, UHX0752, UHX1252, UHX3652, UHX1852 H31 Alarm Alarm code, L04 Alarm Alarm code, L05 Alarm Alarm code