Remote Control Functions

3. Timer Remote Controller (RCS-TM80BG)

12. Outing Function

Outing function is a function that prevents the room temperature from increasing too much (or decreasing too much) when no one is in the room.

An air conditioner works automatically if this function is set effective.

General Performance of the Outing Function

COOL / DRY

The air conditioner starts operation when the room temperature increases up to –1.8°F(1°C) of the upper limit. The air conditioner stops operation when the room temperature decreases up to –3.6°F(2°C) of the upper limit.

„For Example

Setting at Outing Temperature 86°F (30°C)

Outing function Upper limit 86°F(30°C)

(Setting at Outing Temperature)

(ON)

1.8°F(1°C)

 

 

84°F(29°C)

 

 

3.6°F(2°C)

 

 

82°F(28°C)

Room temperature

 

(OFF)

 

 

HEAT

The air conditioner starts operation when the room temperature decreases up to +1.8°F(1°C) of the lower limit. The air conditioner stops operation when the room temperature increases up to +3.6°F(2°C) of the lower limit

„For Example

Setting at Outing Temperature 53°F (12°C) .

Room temperature

(OFF)

 

 

 

 

 

 

 

57°F(14°C)

 

 

 

 

 

 

3.6°F(2°C)

Outing function Lower limit

 

 

(ON)

 

1.8°F(1°C)

 

55°F(13°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

53°F(12°C)

 

 

 

 

 

 

 

 

 

(Setting at Outing Temperature)

 

 

 

 

[Precautions]

The outing control only starts/stops the air conditioner. It does not change the operation mode/temperature setting. Therefore, the operation mode/temperature needs to be set beforehand so that the outing function turns on the air condition- er with your desired operation mode/ temperature setting.

If the room temperature rapidly changes, the room temperature may get over the upper or lower limit when the outing func- tion is activated.

The outing function is invalid during FAN/AUTO operation mode.

The air conditioner's stop order (stated in /above) is valid only when the outing function is operated.

If operated using other remote control unit (or a centralized control device such as a system control), the outing function does not work.

2-27

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8