Trouble Diagnosis

1. Contents of Remote Controller Switch Alarm Display

 

 

ON:

Blinking:

 

 

 

 

OFF:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired

 

 

 

 

 

 

Wireless

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote controller

 

 

 

 

control

 

 

 

 

 

receiver display

 

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible cause of malfunction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

Timer

Standby for heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Serial

Remote controller is

Error in receiving serial communication signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

detecting error signal from

(Signal from main indoor unit in case of group control)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communication

 

<E01>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

errors

indoor unit.

Outdoor system address, indoor unit address, or indoor unit

 

 

 

 

 

Operating

 

 

 

 

 

 

 

address independent/main/sub unit setting has not been made.

 

 

 

 

 

 

lamp blinking

 

 

 

Mis-setting

 

 

 

 

 

 

 

 

 

(Auto address is not completed.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error in transmitting serial communication signal.

 

<E02>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit is detecting error signal from remote controller and system controller.

 

<<E03>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit is detecting error

Error in receiving serial communication signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal from outdoor unit.

When turning on the power supply, the number of connected

 

E04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor units does not correspond to the number set. (Except R.C.

 

 

 

 

 

 

Heating ready

 

 

 

 

 

address is “0.”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lamp blinking

 

 

 

 

 

Group wiring failure of indoor units in the refrigerant system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(occurring when remote controller is operated immediately after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

automatic address setting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit is detecting error

Error in receiving serial communication signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal from indoor unit.

There is an indoor unit which does not send signals when the

 

E06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power is ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Improper setting

Indoor unit address setting is duplicated.

 

<<E08>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duplicated remote controller “main” setting.

 

<<E09>>

 

 

 

 

Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lamp blinking

 

 

Improper setting

Automatic address setting start is prohibited.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AP pin was short-circuited at time when automatic address setting

 

E12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

was started.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit communication

Error of main indoor unit in receiving serial communication signal

 

E18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

error of group control wiring.

from sub indoor units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During auto. address setting,

Number of connected indoor units is less than the number set.

 

E15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of connected units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of connected indoor units is more than the number set.

 

E16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

does not correspond to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number set.

No indoor unit is connected during auto. address setting.

 

E20

 

 

 

 

 

 

 

 

 

 

 

lamp blinking

 

 

 

Main outdoor unit is detecting error signal from sub outdoor unit.

 

E24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duplicated outdoor unit address.

 

E25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mismatch in “No. of outdoor units” setting.

 

E26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error of sub outdoor unit in receiving serial communication signal

 

E29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from main outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Improper setting

Connected indoor unit is not a multi unit.

 

<<L02>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duplication of main indoor unit address setting in group control.

 

<L03>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duplicated indoor unit priority (priority indoor unit).

 

L05

 

 

Operating and heating

 

 

Duplicated indoor unit priority (non-priority indoor unit) and

 

 

 

 

 

 

 

L06

ready lamps blinking

 

 

outdoor unit.

 

simultaneously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Group control wiring is connected to individual control indoor unit.

 

L07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit address is not set.

 

L08

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity code of indoor unit is not set.

 

<<L09>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mismatch of outdoor unit type.

 

L17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duplication of outdoor R.C. address setting.

 

L04

 

 

Operating and heating

 

 

 

ready lamps blinking

 

 

 

 

 

 

 

 

 

 

simultaneously

 

 

 

 

 

 

 

 

Capacity code of outdoor unit is not set.

 

L10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermistor

Indoor unit

Indoor coil temp. sensor (E1)

 

<<F01>>

 

 

Operating and timer

fault

 

Indoor coil temp. sensor (E3)

 

<<F03>>

 

 

lamps blinking

 

 

 

 

 

 

 

 

 

 

alternately

 

 

 

 

 

 

 

 

Indoor suction air (room) temp. sensor

 

<<F10>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor discharge air temp. sensor

 

<<F11>>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continued

3-2