Service Checker

1. Outdoor Unit Maintenance Remote Controller

5. Outdoor Unit Alarm History Monitor

Recalls and displays the outdoor unit alarm history.

This is for the outdoor unit only. Indoor unit alarms cannot be recalled.

The indoor unit alarm history can be viewed on the indoor unit remote controller or other controller.

<Operation procedure>

Press and hold the (CHECK) button and (SET) button simultaneously for 4 seconds or lon- ger to engage outdoor unit alarm history mode.

During temperature monitoring, illuminates. The display and operations are the same as for the alarm history monitor performed from the indoor unit remote controller. However the “unit No.” display shows the outdoor unit address.

Press the (UNIT) button, and select the outdoor unit for which to monitor the alarm history.

1 Press the temperature setting and buttons and select the item code for the alarm

history. The selected outdoor unit address, the item code, and the alarm history (alarm data) are displayed.

2The outdoor unit address is displayed as R.C. XX – YY.

 

(R.C. XX = Outdoor unit system address

 

YY = Outdoor unit address

 

 

 

 

 

3

Item codes 01 – 08 are displayed. 01 indicates the

most recent alarm.

 

 

 

The alarm history displays the alarm code.

 

(If no alarms are present, then

 

 

is

 

 

 

 

 

displayed.)

 

 

 

 

 

4

To clear the alarm history, press

the

(CANCEL) button.

 

 

 

(The outdoor unit alarm history will be cleared.)

 

 

 

 

 

To exit, press the (CHECK) button.

The display returns to the normal display.

5

5

1

4

2

3

6

7

8

6-8