Remote Control Functions

3. Timer Remote Controller (RCS-TM80BG)

Item

Item

 

Setting data

code

No.

Description

 

 

 

 

 

 

 

0000

No forced operation

 

 

 

 

 

Automatic drain pump

0001

Forced operation for 1 minute

 

operation

 

 

 

 

 

 

 

 

0060

Continuous operation

 

Ventilation fan operation

0000

None

 

 

 

 

0001

Ventilation fan operated by remote controller.

 

 

 

 

 

 

 

Wired remote controller sensor

0000

Not used. (Body sensor is used.)

 

 

 

 

0001

Remote control sensor is used.

 

 

 

“Operation change control in

0000

Normal (displayed)

 

progress” display

0001

Not displayed

 

OFF reminder function for

0000

None

 

when weekly timer is used

0001

Only stop time setting is enabled.

 

Discharge temperature control

0000

Discharge temperature control OFF

 

 

 

 

0001

Discharge temperature control ON

 

 

 

 

 

 

 

RAP valve

0000

RAP valve control OFF

 

 

 

 

0001

RAP valve control ON

 

 

 

 

 

 

 

 

0013

Control temperature 55°F (13°C )

 

Heat exchanger temperature

 

 

 

0014

Control temperature 57°F (14°C )

 

for cold air discharge

 

 

 

 

 

 

(Heat exchanger control point

 

 

 

0025

Control temperature 77°F (25°C )

 

for control to prevent cold air)

 

 

0026

Control temperature 78°F (26°C )

 

 

 

 

 

 

0000

Output linked with fan. (ON when indoor unit fan is

 

Fan output switching

operating.)

 

 

 

 

0001

Fan mode operation output

 

 

0000

No delayed start

 

 

0001

1 sec. delayed start

 

 

 

 

 

 

0002

2 sec. delayed start

 

Drain pump delayed start time

 

 

 

 

 

 

 

 

 

 

 

0058

58 sec. delayed start

 

 

 

 

 

 

0059

59 sec. delayed start

 

 

 

 

 

 

0060

60 sec. delayed start

 

 

 

 

 

 

0000

Humidifier output OFF. Drain pump stopped.

 

 

 

 

 

 

0001

Humidifier output ON. Drain pump operates.

 

Humidifier setting

 

 

 

0002

Humidifier output ON. Drain pump operates for 1 minute

 

 

when total humidifier operating time reaches 60 minutes.

 

 

 

 

 

 

 

 

 

0003

Humidifier output ON. Drain pump stopped.

 

 

 

 

 

 

0000

Standard setting

 

Flap operation mode

 

 

 

0001

Draft reduction mode (Flap swing lower-limit position is

 

 

upwards.)

 

 

 

 

 

0000

Smudging reduction mode (Flap swing upper-limit position

 

 

is shifted downwards.)

 

 

 

 

Flap swing mode

0001

Normal mode

 

 

0002

Draft reduction mode (Flap lower-limit position is shifted

 

 

shifted upwards.)

 

 

 

2-36