Trouble Diagnosis

3. W-2WAY ECO-i Alarm Codes

F31 Alarm

Alarm code

F31

 

 

Alarm meaning

Outdoor unit non-volatile memory (EEPROM) trouble

Alarm conditions

(1)

Non-volatile memory is not present when power initialization occurs.

 

(2)

Read values do not match after writing to non-volatile memory is complete.

Probable cause

(1)

Memory was not inserted after the PCB was replaced.

 

(2) The lifetime of the non-volatile memory has been reached.

 

(3)

Non-volatile memory is installed incorrectly (wrong direction, bent pins, etc.).

Check

(1)

Check the non-volatile memory on the PCB.

Correction

 

Example

 

Notes

 

 

 

 

H03 alarm

 

 

 

 

Alarm code

H03

 

 

Alarm meaning

Compressor CT sensor disconnected or short-circuit

 

 

Alarm conditions

Alarm occurs if the current value is 1.5 A or less when 2 seconds or longer have elapsed after

 

output from that compressor started.

 

* No current is detected even though the compressor is operating.

Probable cause

(1)

CT circuit failure (including cut wiring, etc.)

 

(2)

Disconnected CT circuit connector

 

(3) This CT circuit is connected to the connector of the other CT circuit.

 

(4)

PCB failure

 

(5)

Noise

Check

(1)

CT circuit failure, PCB failure

 

 

Trouble: • Current value during compressor operation is below the threshold value.

 

 

Check: • Check that the connector is not disconnected.

 

 

• Check the continuity of the CT circuit.

 

 

Install a normal CT in place of this CT and check. If current is detected, then the

 

 

PCB can be judged OK.

 

 

CT circuit failure

 

 

• Check that current is flowing in the phase where the CT circuit is connected.

 

 

Check voltage and current.

 

(2)

Crossed wiring or installation error

 

 

Trouble: When the compressor is stopped, the current value at the other compressor is high.

 

(3)

If the cause is still unknown after checking the above, then it is possible that noise is the

 

 

cause of the trouble. It is necessary to connect a PC or other instrument.

 

 

 

Correction

(1)

Replace the CT circuit.

 

(2)

Replace the outdoor unit PCB.

 

(3)

Correct the problem.

Example

(1) The connector was not inserted after the PCB was replaced.

Notes

Use a normal CT as a tool to determine whether the trouble is a PCB failure or CT failure.

3-12

Page 74
Image 74