Specifying the delay time

Since the tag limits for CONTENT_T1, CONTENT_T2 and CONTENT_T3 are specified by additional tags, the delay times have to be programmed in the properties under Trigger Settings. This is necessary because these tags are not updated with the controller when the panel is powered up, and these alarms are displayed in the alarm window as a result. Twice the period of the acquisition cycle of the tag should be used for this.

Enter a delay of 200 milliseconds for CONTENT_T1, CONTENT_T2 and CONTENT_T3.

SCE Training Curriculum

Page 102 of 118

To be used only at Educational and R&D Facilities

TIA Portal Module 090-010, Edition 03/2013

 

Unrestricted / © Siemens AG 2013. All Rights Reserved

SCE_EN_090-010_R1209_ WinCC Advanced with Runtime and TP700 Comfort Panel