Siemens X-400 technical specifications Installation and Commissioning, Switch, Status, Meaning

Models: X-400

1 148
Download 148 pages 53.7 Kb
Page 102
Image 102
Switch

Installation and Commissioning

Notice

Changing the switch settings during operation causes fault displays and activates the signaling contact. The settings are adopted only after the device is restarted.

The RM switch allows you to configure the SCALANCE X414-3E as a redundancy manager in a ring with redundancy manager.

The STBY switch is reserved for future functionality and does not currently have any function.

With switches R1 and R2, you can specify either the two ports in slot 5, the two ports in slot 6 or the first ports of slots 6 and 7 as ring ports. If you do not want any ring ports defined, both switches must be set to ON.

Switch

Status

Meaning

 

 

 

RM

OFF

SCALANCE X414-3E is not a redundancy manager.

 

 

 

 

ON

SCALANCE X414-3E is a redundancy manager.

 

 

 

STBY

OFF

No function, reserved for future applications.

 

ON

 

 

 

 

R1

OFF

Ports in slot 5 (gigabit ports) are ring ports.

R2

OFF

 

 

 

 

R1

ON

Ports 1 and 2 of slot 6 are ring ports.

R2

OFF

 

 

 

 

R1

OFF

Port 1 of slot 6 is first ring port.

R2

ON

Port 1 of slot 7 is second ring port.

 

 

 

R1

ON

No ring redundancy.

R2

ON

 

 

 

 

When shipped, the factory settings apply (see section 6.5).