Siemens X-400 Display in Display Mode D, IN1/IN5, IN2/IN6, Stby, IN3/IN7, IN4/IN8

Models: X-400

1 148
Download 148 pages 53.7 Kb
Page 110
Image 110
Display in Display Mode D

Installation and Commissioning

Display in Display Mode D

In display mode D, both the DM1 and DM2 LEDs of the Switch CPU are on. This mode indicates whether the power supply is being monitored with the signaling contact.

F

IN1/IN5

RM

P1

L1

IN2/IN6

STBY

P2

L2

IN3/IN7

DM1

 

 

IN4/IN8

DM2

 

PowerModuleLEDs

DI-LEDs

CPU-LEDs

Port-LEDs

Figure 6-26 LED display of the power module and the Switch CPU in DMode D

The following table shows the meaning of the three light emitting diodes on the power module in display mode D:

Label

Color

Status

Meaning

 

 

 

 

F

 

off

No problem has been detected by the

 

 

 

SCALANCE X414-3E.

 

 

 

 

 

Red

on

The SCALANCE X414-3E has detected a

 

 

 

problem. The signaling contact opens.

 

 

 

 

L1

 

off

Power supply L1 is not monitored. If L1 falls

 

 

 

below 17 V, the signaling contact does not

 

 

 

respond.

 

 

 

 

 

Green

on

Power supply L1 is monitored. If L1 falls

 

 

 

below 17 V, the signaling contact responds.

 

 

 

 

L2

 

off

Power supply L2 is not monitored. If L2 falls

 

 

 

below 17 V, the signaling contact does not

 

 

 

respond.

 

 

 

 

 

Green

on

Power supply L2 is monitored. If L2 falls

 

 

 

below 17 V, the signaling contact responds.

 

 

 

 

110

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches

C79000-G8976-C186-03

Page 110
Image 110
Siemens X-400 technical specifications Display in Display Mode D, IN1/IN5, IN2/IN6, Stby, IN3/IN7, IN4/IN8