Technical Specifications

Interfaces

 

Load on the signaling contact

24 V DC / max. 100 mA safety extra-

 

low voltage (SELV)

Overcurrent protection at input

Non-replaceable fuse

 

(F 3.15 A / 250 V)

Digital Inputs

Input voltage:

 

Rated value 24 V DC safety extra-

 

low voltage (SELV)

 

For state "1“: + 13 V ...+ 30 V

 

For state "0“: – 30 V... + 3 V

 

Max. input current: 8 mA

 

Max. cable length: 30 m

 

Inputs isolated from electronics.

 

 

C-Plug

 

Dimensions (width x height x depth)

24.3 x 17.0 x 8.1 mm

Weight

approx. 5 g

Power consumption

0.015 W

 

 

Memory capacity

32 Mbytes

 

 

 

 

Permitted Cable Lengths

 

TP cable length

With TP cord up to 10 m,

 

with FastConnect cabling system up to

 

100 m.

 

 

Cascading Depth

 

Line/star structure

Any (only depending on signal propa-

 

gation time)

Ring with redundancy manager

50 (for reconfiguration time < 0.3 s)

 

 

 

 

Switching Properties

 

Max. number of learnable addresses

8000

Aging time (default)

40 s

Switching procedure

Store and forward

Latency (store and forward time)

5 µs

 

 

120

Operating Instructions for SCALANCE X-400 Industrial Ethernet Switches

C79000-G8976-C186-03

Page 120
Image 120
Siemens X-400 technical specifications Plug, Permitted Cable Lengths, Cascading Depth, Switching Properties