Electrical Installation

5

 

 

5.7Correction of supply current

Attention in case of continous load: Due to the capacitive input impedance of DC-Bus, the input current is deformated.

This guides to RMS -values higher than the sinus-based calculated values. Fuses, contactors and line filters have to be selected in respect to this effect.

In typical servo application with Stop/Go-operation (S3-Operation), the rating to nominal data will be sufficient.

In other cases, the value has to be corrected using the following diagram.

Example:

Drive type 637f/KD6R16.S5-7 is supplied by AC 230V 3-ph. Output-power: Pout = 200V x 16A x 1,73 = 5,54 kW

This output-power must be generated by:

calculated supply-current Iac sinus = 5,54kW / (230V x 1,73) = 13,9 A Correction-Factor from diagram: 1,6

RMS. Supply-Current Ieff = Iac sinus x 1,6 = 22,3 A

Result:

All supply-equipment has to be selected in respect to the enhanced current.