6

Wiring Instructions

 

 

Electromagnetic compatibility (EMC)

6.7.1Hints for mounting

AAll components are mounted inside of

a steel control cubicle on a mounting plate

(thickness min. 3mm).

 

 

 

 

3mm

Recommended: Galvanizing

 

 

 

 

 

 

 

 

 

 

 

BThe connection between drive housing filter-

housing and mountig-plate must be blank and not reduced by varnish. All screws must be well fixed !

CUse only SSD Drives-filters and cables for motor and resolver

DPlace all wires and cables as close as possible

to any grounded metal parts

E

Separate power- and control cables. Minimum

 

 

 

distance: 0,3m

 

 

 

crosspoints: 90°

0,3 m

90°

FAvoid cable-loops. Especially the line between line-filter and drive has to be as close and short

as possible (drilled)

G Maintain screen as close as possible to the cable-end (max distance 8 cm)

8 cm max

HConnect screen-connections according to

general view of connetions, see chapter 2.1. Ground screens on both sides, shortest way. For long cables: Connect additional screen-area along the way

IConnect screens area-contacted to good

grounded points

KConnect unused wires in cables to ground

LInstall control cables directly close to grounded metal-parts or screend when leaving the control- cubicle

M Take care for good grounding of control- transformer (DC 24V). Use transformer with metal-socket and take care for conductive contact to mounting-plate

NTake care for good general grounding of the

complete system. Interconnect several mounting-plates with copper-rails or copperband. Take care for ground connection between control-cubicle and machine !

________________________________________________________________________________________________________________________________________________________________________________________________________________________

58

Product Manual Type: 637f

07-02-10-01-E-V0505.doc