2.2.2.1Verify Chassis Fan Tray Upgrade

Caution – The Sun Netra CT 900 server fan tray upgrade kit (594-4953) must be installed in the chassis before the Sun Netra CP3220 blade server is installed. This fan tray upgrade is required to provide adequate cooling and prevent the system from overheating or shutting down due to an over temperature condition that can occur with the older fan trays.

To verify if the fan tray upgrade is installed on a Sun Netra CT 900 server, log into the Shelf Manager and issue the following command for fan trays 1,2, and 3:

#clia fruinfo fan_tray 1 grep "Product Part"

If "Product Part / Model Number = 371-3033-xx", an upgraded fan tray is installed. If "Product Part / Model Number" is not 371-3033, an old fan tray is installed and the upgrade is required. Refer to the Sun Netra CT 900 Server Upgrade Guide (820-3255) for more information.

2.2.2.2Installing Optional Components

Use the following table to locate your options and installation instructions.

DIMMs

Section 2.3.6.1, “DIMM Requirements” on page 2-19

 

Section 2.3.6.2, “Installing a DDR2 DIMM” on page 2-21

Compact Flash card

Section 2.3.7, “Installing the Optional Compact Flash Card” on

 

page 2-24

AMC card

Section 2.3.8, “Installing Optional AMC Cards” on page 2-26

 

 