Toshiba RAV-SM560UT-E Systematic Refrigerating Cycle Diagram, Indoor unit, Outdoor unit, 20

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 20
Image 20
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

Indoor Unit/Outdoor Unit

RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM560KRT-E/RAV-SM560AT-E

Indoor unit

Air heat exchanger

TC sensor

Outer diameter of refrigerant pipe

Gas side ØA

Liquid side ØB

 

 

12.7mm

6.4mm

 

 

TCJ sensor

TS sensor

TD sensor

4-way valve (VT7101D)

Refrigerant pipe

Refrigerant pipe

at liquid side

at gas side

Outer dia. ØB

Outer dia. ØA

Max 30m

Packed valve

 

Packed valve

Outer dia. ØB

Outdoor unit

Outer dia. ØA

 

 

 

 

PMV

 

 

(SKV-18D26)

TO sensor

 

 

 

 

Strainer

 

TE

 

 

sensor

 

Muffler

Ø19 × L160

Rotary compressor

(DA130A1F-23F)

Heat exchanger Ø8 multiple thread ripple 1 row 22 stages FP1.3 flat fin

Distributor

R410A 0.9 kg

Cooling

Heating

 

 

 

Pressure

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor heat

Outdoor heat

Indoor

temp. conditions

 

 

(MPa)

(kg/cm²G)

 

 

revolutions per

 

 

Discharge

Suction

(DB/WB) (°C)

 

 

 

 

 

 

 

 

exchanger

exchanger

second (rps)

fan

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

*

 

Indoor

Outdoor

 

Standard

3.1

0.9

31.9

8.9

85

15

10

50

74

HIGH

27/19

35/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.6

1.0

37.1

10.4

93

20

15

57

72

HIGH

32/24

43/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

0.9

0.7

9.1

7.1

20

7

3

5

28

LOW

18/15.5

–5/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.3

0.6

23.6

6.2

71

1

39

3

84

HIGH

20/–

7/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.3

1.2

33.2

11.8

78

20

54

19

47

LOW

30.–

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.7

0.2

16.4

1.8

110

–20

26

–22

110

HIGH

15/–

–20/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*4 poles are provided to this compressor.

The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.

– 20 –

Page 20
Image 20