Toshiba RAV-SM800UT-E, RAV-SM800AT-E 109, <Wireless remote controller type>, aOutline of Judgment

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 109
Image 109
(a)Outline of Judgment

(a)Outline of Judgment

A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.

<Judgment by flashing display on the indoor unit display part>

The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part.

Remote

Block display

Contents of self-diagnosis

Check code

controller code

 

 

 

 

 

 

 

Operation lamp display flashes. (1Hz)

Power failure (In power ON)

——

 

 

 

 

00

Operation lamp display flashes. (5Hz)

Indoor P.C. board

0b to 0F, 11, 12, b5, b6

 

 

 

 

01

Operation/timer lamp displays flash. (5Hz)

Inter-unit cables/transmission system

04

 

 

 

 

02

Operation/defrost lamp displays flash. (5Hz)

Outdoor P.C. board

14 to 19, 1A, 1C

 

 

 

 

03

Operation/timer/defrost lamp displays flash. (5Hz)

Cycle system, etc.

1d, 1E, 1F, 21

 

 

 

 

——

——

1b, 8b

 

 

 

 

(b)Self-diagnosis by check code on the remote controller

Refer to Judgment of error mode by check code on the remote controller.

<Wireless remote controller type>

1. Before troubleshooting

1) Required tools/instruments

+ and screwdrivers, spanners, radio cutting pliers, nippers, etc.

Tester, thermometer, pressure gauge, etc.

2)Confirmation points before check

The following operations are normal.

a)Compressor does not operate.

Is not 3-minutes delay (3 minutes after compressor OFF)?

Does not thermostat turn off?

Does not timer operate during fan operation?

Is not outside high-temperature operation controlled in heating operation?

b)Indoor fan does not rotate.

Does not cool air discharge preventive control work in heating operation?

c)Outdoor fan does not rotate or air volume changes.

Does not high-temperature release operation control work in heating operation?

Does not outside low-temperature operation control work in cooling operation?

Is not defrost operation performed?

d)ON/OFF operation cannot be performed from remote controller.

Is not forced operation performed?

Is not the control operation performed from outside/remote side?

Did you return the cabling to the initial positions?

ƒAre connecting cables between indoor unit and receiving unit correct?

109

Page 109
Image 109
Toshiba RAV-SM800UT-E, RAV-SM800AT-E 109, <Wireless remote controller type>, aOutline of Judgment, Before troubleshooting