Toshiba RAV-SM560UT-E, RAV-SM800AT-E Control Specifications, Outline of specifications, Remarks

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 50
Image 50
9-1-3. Control Specifications

9-1-3. Control Specifications

No.

Item

 

 

Outline of specifications

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

1

When power

1) Distinction of outdoor units

 

 

 

 

 

 

 

supply is reset

 

When the power supply is reset, the outdoors are

 

 

 

 

 

distinguished, and control is exchanged according to

 

 

 

 

 

the distinguished result.

 

 

 

 

 

 

 

 

2) Setting of the indoor fan speed

 

 

 

 

 

 

 

Based on EEPROM data, rspeed of the indoor fan is

Air speed

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Operation mode

1) Based on the operation mode selecting command

 

 

 

selection

 

from the remote controller, the operation mode is

 

 

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

Outline of control

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

 

Air conditioner stops.

 

 

 

 

 

 

 

FAN

 

Fan operation

 

 

 

 

 

 

 

COOL

 

Cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY

 

Dry operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

Heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ta

: Room temperature

 

 

 

AUTO

 

Ta

COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

( C)

 

 

Ts

: Setup temperature

 

 

 

 

 

+3

 

 

(COOL ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tsc : Setup temperature

 

 

 

 

 

Tsc

 

 

 

 

 

 

 

 

 

or Tsh

 

(COOL OFF)

 

 

 

in cooling operation

 

 

 

 

 

3

 

 

 

Tsh : Setup temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

in heating operation

1)Judge the selection of COOL/HEAT mode as shown in the figure below.

When the heating operation (Thermo OFF) is exchanged to cooling operation if Tsh exceeds +3 or more.

(COOL OFF) and (COOL ON) in the figure indicate an example.

When the cooling operation (Thermo OFF) is exchanged to heating operation if Tsc exceeds -3 or less.

2)For the automatic capacity control after judgment of COOL/HEAT, refer to item 4.

3)For the temperature correction of room temperature control in automatic heating operation, refer to item 3.

3 Room tempera-

1) Adjustment range Remote controller setup tempera-

 

 

 

 

 

 

 

 

ture control

 

ture (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL/

 

 

Heating

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY

 

 

operation

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard type

 

18 to 29

 

18 to 29

 

18 to 29

 

Max. setup temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless type

 

17 to 30

 

17 to 30

 

19 to 29

 

 

 

 

 

 

 

Ts (Max) = 35°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

 

5

 

4

3

 

2

1

Standard

1

2

3

4

5

 

 

 

setup temp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp (°C)

 

19

 

20

 

21

 

22

 

23

 

24

 

25

26

27

 

28

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Differential 1K (=deg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) In heating operation, the setup temperature can be

 

 

 

 

 

 

 

 

 

 

corrected by using Dip switch (SW03) on the indoor

 

 

 

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW03

 

1

 

 

ON

 

ON

 

OFF

OFF

 

 

 

SW03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

ON

 

OFF

 

ON

OFF

 

 

1

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp correction

 

 

+0°C

 

+2°C

+4°C

+6°C

 

 

ON

 

 

OFF

 

50

Page 50
Image 50
Toshiba RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM800UT-E service manual Control Specifications, Outline of specifications, Remarks