9-1-3. Control Specifications

No.

Item

 

 

Outline of specifications

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

1

When power

1) Distinction of outdoor units

 

 

 

 

 

 

 

supply is reset

 

When the power supply is reset, the outdoors are

 

 

 

 

 

distinguished, and control is exchanged according to

 

 

 

 

 

the distinguished result.

 

 

 

 

 

 

 

 

2) Setting of the indoor fan speed

 

 

 

 

 

 

 

Based on EEPROM data, rspeed of the indoor fan is

Air speed

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Operation mode

1) Based on the operation mode selecting command

 

 

 

selection

 

from the remote controller, the operation mode is

 

 

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

Outline of control

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

 

Air conditioner stops.

 

 

 

 

 

 

 

FAN

 

Fan operation

 

 

 

 

 

 

 

COOL

 

Cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY

 

Dry operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

Heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ta

: Room temperature

 

 

 

AUTO

 

Ta

COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

( C)

 

 

Ts

: Setup temperature

 

 

 

 

 

+3

 

 

(COOL ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tsc : Setup temperature

 

 

 

 

 

Tsc

 

 

 

 

 

 

 

 

 

or Tsh

 

(COOL OFF)

 

 

 

in cooling operation

 

 

 

 

 

3

 

 

 

Tsh : Setup temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

in heating operation

1)Judge the selection of COOL/HEAT mode as shown in the figure below.

When the heating operation (Thermo OFF) is exchanged to cooling operation if Tsh exceeds +3 or more.

(COOL OFF) and (COOL ON) in the figure indicate an example.

When the cooling operation (Thermo OFF) is exchanged to heating operation if Tsc exceeds -3 or less.

2)For the automatic capacity control after judgment of COOL/HEAT, refer to item 4.

3)For the temperature correction of room temperature control in automatic heating operation, refer to item 3.

3 Room tempera-

1) Adjustment range Remote controller setup tempera-

 

 

 

 

 

 

 

 

ture control

 

ture (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL/

 

 

Heating

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRY

 

 

operation

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard type

 

18 to 29

 

18 to 29

 

18 to 29

 

Max. setup temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless type

 

17 to 30

 

17 to 30

 

19 to 29

 

 

 

 

 

 

 

Ts (Max) = 35°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

 

5

 

4

3

 

2

1

Standard

1

2

3

4

5

 

 

 

setup temp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp (°C)

 

19

 

20

 

21

 

22

 

23

 

24

 

25

26

27

 

28

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Differential 1K (=deg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) In heating operation, the setup temperature can be

 

 

 

 

 

 

 

 

 

 

corrected by using Dip switch (SW03) on the indoor

 

 

 

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup at shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW03

 

1

 

 

ON

 

ON

 

OFF

OFF

 

 

 

SW03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

ON

 

OFF

 

ON

OFF

 

 

1

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup temp correction

 

 

+0°C

 

+2°C

+4°C

+6°C

 

 

ON

 

 

OFF

 

50

Page 50
Image 50
Toshiba RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM800UT-E, RAV-SM560AT-E, RAV-SM560BT-E Control Specifications, Heating operation

RAV-SM800BT-E, RAV-SM560BT-E, RAV-SM560AT-E, RAV-SM560UT-E, RAV-SM800UT-E specifications

Toshiba offers a range of innovative air conditioning units designed for optimal performance and efficiency, including the RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM560BT-E, and RAV-SM800BT-E models. Each of these units is part of Toshiba's commitment to quality air conditioning solutions that cater to both residential and commercial spaces.

The RAV-SM800UT-E and RAV-SM800AT-E models are notable for their impressive cooling and heating capacities, making them ideal for larger spaces. They feature advanced inverter technology, which adjusts the compressor's speed to maintain a consistent temperature while reducing energy consumption. This not only ensures comfort but also translates into significant energy savings over time.

In terms of design, these models benefit from Toshiba's sleek and modern aesthetics, allowing them to blend seamlessly into various interior styles. The noise levels are remarkably low, thanks to Toshiba's engineering, making these units suitable for use in environments where quiet operation is paramount, such as offices and bedrooms.

The RAV-SM560UT-E and RAV-SM560BT-E models offer similar performance but are tailored for smaller spaces without compromising on efficiency. They include features such as multilayer air filtration systems that effectively remove dust, allergens, and other pollutants, ensuring a healthier indoor air environment. Furthermore, they come equipped with intelligent control options, allowing users to operate the units remotely via smartphone applications.

Another standout characteristic of the RAV-SM800BT-E is its ability to provide both cooling and heating, making it a versatile option throughout the year. These units utilize R32 refrigerant, which has a lower global warming potential compared to traditional refrigerants, aligning with Toshiba's commitment to sustainability.

Each of these models is designed for easy installation and maintenance, featuring a user-friendly interface and robust build quality. The advanced diagnostics feature allows for timely troubleshooting and maintenance, ensuring the longevity of the units.

In summary, Toshiba's RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM560BT-E, and RAV-SM800BT-E models represent a blend of innovative technology, user-centric design, and environmental responsibility. These units not only deliver exceptional climate control but also contribute to reducing energy costs and improving indoor air quality, making them a smart choice for a wide range of applications.