Toshiba RAV-SM560BT-E, RAV-SM800AT-E, RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM560AT-E P12 error/11 error

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 76
Image 76
[P12 error]/[11 error]

[P12 error]/[11 error]

<Only for 4-way air discharge cassette type models (RAV-SM560UT-E/RAV-SM800UT-E)>

Turn off the power.

 

 

 

 

 

 

 

Are not there connections errors or

YES

disconnection on connectors CN333 and CN334

 

of indoor unit P.C. board (MCC-1402)?

 

 

NO

 

 

 

 

 

 

Remove connectors CN333 and CN334 of indoor unit P.C. board (MCC-1402).

Does the fan rotate without trouble

NO

 

when handling the fan with hands?

 

 

YES

 

 

 

 

 

 

– 76 –Manual background Correct connection of connector.

Replace indoor fan motor.

Are resistance values between phases

at fan motor connector CN333 motor side of indoor P.C. board (MCC-1402) correct? *1

YES

Is resistance value of fan motor connector CN333 at motor side of indoor P.C. board (MCC-1402) correct? *2

YES

Is signal output of indoor fan motor

position detection correct? *3

YES

Check indoor P.C. board (MCC-1402).

Defect Manual background Replace

NOManual backgroundManual background Replace indoor fan motor.

*1

Are not coil windings between 1 (Red lead) and 3 (White lead), between 3 (White lead) and 5 (Black lead), between

5(Black lead) and 1 (Red lead) opened or shorted? Manual background For resistance, see the following values. AIU-P401H/HR, P451, P501, P561, P631, P711, P801 Manual background Approx. 70 to 100Manual background

AIU-P1121H/HR, P1401, P1601 Manual background Approx. 35 to 50Manual background

Is not earthed between cabinet and 1, 3, 5 Manual background 10MManual background or more

NOManual background Replace indoor fan motor.

*2

Check resistance of fan motor position detection circuit.

Is not coil winding between 1 (Yellow lead) and 4 (Pink lead) opened or shorted? Manual background Resistance: Approx. 5 to 20kManual background

NOManual background Replace indoor fan motor.

*3

Check fan motor position detection signal.

Using a tester, measure the voltage between CN334 1 and 5 of indoor P.C. board (MCC-1402) under condition that CN333 and CN334 are mounted and the power is turned on.

Manual background Rotate the fan slowly with hands, and check the pin voltage

swings between 0 to 5V voltage.

Between 4 and

5 : 5V

CN333

 

 

CN334

76

Page 76
Image 76