Toshiba RAV-SM560AT-E, RAV-SM800AT-E, RAV-SM800UT-E 75, P10 error/Ob error, F10 error 0C error

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 75
Image 75
[P10 error]/[Ob error]

[P10 error]/[Ob error]

Is connection of float switch connector

NO

 

(Indoor control P.C. board CH34) normal?

 

 

YES

 

 

 

 

 

 

NO

Does float switch operate?

YES

NO

Is circuit cabling normal?

YES

Correct connection of connector.

Check and correct cabling/wiring.

NO

Does drain pump operate?

YES

NO

Is power of drain pump turned on?

YES

 

 

 

 

 

 

 

 

Check drain pipe, etc.

 

 

 

Replace drain pump.

 

 

 

 

 

 

Check cabling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check indoor P.C. board (MCC-1402 or MCC-1403). Defect [F10 error] [0C error] Replace

Check indoor P.C. board (MCC-1402 or MCC-1403). Defect – 75 – Replace

[F10 error] [0C error]

Is connection of TA sensor connector (indoor P.C. board CN104) normal?

YES

Are characteristics of TA sensor

resistance value normal?

YES

Check indoor P.C. board (MCC-1402 or MCC-1403). Defect Manual background Replace

NO

NO

* Refer to Characteristics-1.

Correct connection of connector.

Replace TA sensor.

75

Page 75
Image 75
Toshiba RAV-SM560AT-E, RAV-SM800AT-E, RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM560BT-E 75, P10 error/Ob error, F10 error 0C error