No.

Item

Outline of specifications

Remarks

5 Air volume control

 

 

 

 

 

 

 

 

Air volume setup

SM560

SM800

 

 

(Continued)

 

 

 

Tap

 

 

 

 

 

 

 

COOL, DRY, FAN

HEAT

Revolutions per

 

 

 

 

minute (rpm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F4

 

UH

1290

1480

 

 

 

 

 

 

 

 

 

 

 

F5

 

H

1230

1480

 

 

 

 

 

 

 

 

 

 

 

F6

H

 

1180

1340

 

 

 

 

 

 

 

 

 

 

 

F7

M+

M+

1150

1320

 

 

 

 

 

 

 

 

 

 

 

F8

 

M

1120

1310

 

 

 

 

 

 

 

 

 

 

 

F9

M

 

1060

1200

 

 

 

 

 

 

 

 

 

 

 

FA

 

L+

1060

1200

 

 

 

 

 

 

 

 

 

 

 

FB

L+

L

990

1100

 

 

 

 

 

 

 

 

 

 

 

FC

L

 

940

1040

 

 

 

 

 

 

 

 

 

 

 

FD

 

UL

900

900

 

 

 

 

 

 

 

 

 

 

3) In heating operation, the mode changes to [Ultra

Stopis a cool air

 

Low (UL)] or [STOP] if thermostat is turned off.

discharge preventive

4) If Ta

25°C when heating operation has started and

controloperation by Tc.

 

when defrost operation has been cleared, it oper-

Tc: Indoor heat exchanger

 

ates with MED mode or higher mode for 1 minute

sensor temp.

 

from when Tc has entered in A zone of cool air

 

 

discharge preventive control (Item 6).

 

 

 

5)In automatic cooling/heating operation, the revolu- tion frequency of [HIGH (H)] is set larger than that in the standard cooling/heating operation. However the revolution frequency is restricted in the automatic heating operation as shown in the following figure.

Tc

F5

F4

 

 

( C)

 

 

47

 

 

42

 

 

 

F4

 

 

6) (For wireless type only) The mode enters [AUTO] in

Display: [AUTO]

 

automatic cooling/heating operation.

 

 

7) The mode enters [LOW (L)] during Dry operation

 

 

 

 

 

 

6 Cool air discharge

1) In heating operation, the indoor fan is controlled

 

preventive control

based on the detected temperature of Tc sensor.

 

 

As shown below, the upper limit of the revolution

 

 

frequency is determined.

 

Display in C zone

 

 

 

 

 

A zone : Setup air volume

Display of main unit:

 

 

 

 

 

from remote

Defrost LED goes on.

 

 

 

 

 

controller

 

Tc( C)

 

 

 

A

B zone : Low air

When wired remote

 

30

 

 

 

 

 

C zone : OFF

 

 

 

 

controller is installed:

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

 

 

PRE-HEAT/DEFROST

 

 

 

 

 

 

 

 

 

 

 

goes on remote controller.

 

20

 

C

B

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

52

Page 52