Image 45
RBC-AMT21
1) When the fan operation has started, positioning of the stator and the rotor are performed.
(Moves slightly with tap sound)
2) The motor operates according to the command from the indoor controller.
Normal control
Max. frequency is restricted to approximately the rated heating frequency
3) HEAT operation mode: the frequency is controlled according to
the right figure if To > 15°C.
4
3
Ta( C)
Tsh
Tsc
1) This control is operated by selecting [AUTO] opera- tion mode.

No.

Item

 

Outline of specifications

Remarks

14

Central control

1)

Setting at the central controller side enables to select

 

 

mode selection

 

the contents which can be operated on the remote

 

 

 

 

controller at indoor unit side.

 

 

 

2)

RBC-AMT21

 

 

 

 

[Last push priority] :

(No display)

 

 

 

The operation contents can be selected from both

 

 

 

 

remote controller and central controller of the indoor

 

 

 

 

unit side, and the operation is performed with the

 

 

 

 

contents selected at the last.

 

 

 

 

[Center] :

[CENTER] goes on.

 

 

 

Start/Stop operation only can be handled on the

 

 

 

 

remote controller at indoor unit side.

 

 

 

 

[Operation Prohibited] :

[CENTER] goes on.

 

 

 

It cannot be operated on the remote controller at

In a case of wireless type, the

 

 

 

indoor unit side. (Stop status is held.)

display lamp does not change.

 

 

 

 

However, contents which can be

 

 

 

 

operated are same.

 

 

 

 

The status set in [CENTER]/

 

 

 

 

[Operation Prohibited] mode is

 

 

 

 

notified with the receiving sound

 

 

 

 

Pi, Pi, Pi, Pi, Pi(5 times).

 

 

 

 

 

15

Energy-save

1)

Selecting [AUTO] mode enables an energy-saving to

 

 

control

 

be operated.

 

 

(By connected

2)

The setup temperature is shifted (corrected) in the

 

 

outdoor unit)

 

range not to lose the comfort ability according to input

 

 

 

 

values of various sensors.

 

 

 

3) Data (Input value room temp. Ta, Outside temp. To, Air

 

 

 

 

volume, Indoor heat exchanger sensor temp. Tc) for

 

 

 

 

20 minutes are taken the average to calculate

 

 

 

 

correction value of the setup temperature.

 

 

 

4)

The setup temperature is shifted every 20 minutes,

 

 

 

 

and the shifted range is as follows.

 

 

 

 

In cooling time : +1.5 to 1.0K

 

 

 

 

In heating time : 1.5 to +1.0K

 

16 Max. frequency

cut control

2) COOL operation mode: the frequency is controlled

according to

Ta( C)

Normal control

 

 

the following

 

 

+4

 

figure if

 

 

 

 

 

 

 

To < 28°C.

+3

Max. frequency is restricted

to approximately the rated

cooling frequency

17 DC motor (For 4-way air discharge cassette type only)

NOTES :

When the fan rotates while the air conditioner stops due to entering of outside air, etc, the air conditioner may operated while the fan motor stops.

When a fan locking is found, the air conditioner stops, Check code [P12] and an error is displayed.