Invalid address No. setup from remote controller

12-3. How to Set an Address Number

When connecting indoor units to the central control remote controller by using a network adapter, it is required to set up a network address No.

The network address No. should be agreed with the line No. of the central control remote controller.

When the unit was shipped from the factory, the network address has been set to 1.

The following two methods to set the network address are provided.

1. How to set from the remote controller at indoor unit side

* This method is effective only when of set switch SW01 on the network adapter P.C. board is turned off.

<Procedure> Set the network address while the unit stops.

1 Push

+

Fig. 1

buttons for 4 seconds or more.

In the group control, the unit No RLL is displayed,

 

 

 

 

 

and then all the indoor units in the group control are

 

SET DATA

 

 

 

selected. In this time, fans of all the selected indoor

 

 

 

 

 

 

UNIT No.

 

units are turned on. (Fig. 1)

 

 

 

R.C.

No.

 

(Keep status of RLL display without pushing

 

 

 

 

 

button.)

 

 

 

 

3

 

 

 

 

For the individual remote controller which is not

 

 

 

 

included in a group control, the line address and the

1

 

 

 

2

indoor unit address are displayed.

5

 

 

UNIT

 

 

 

2 Specify the item code 03 using the temperature

SET

CL

 

 

 

 

 

 

 

setup

/

buttons.

 

 

4

 

 

 

3 Using the timer time

/

buttons, select the

 

 

 

 

setup data.

 

Table 1

The setup data are shown in the right table (Table 1).

 

 

 

Setup data

Network address No.

4 Push SET

 

button. (OK if display goes on)

 

 

0001

1

To change the item to be set, return to 2.

0002

2

0003

3

5 Push

 

button.

:

:

0064

64

The status returns to the usual stop status.

 

 

0099

Unset (Setup at shipment from factory)

 

 

 

 

 

 

2. How to set by the switch on the network adapter P.C. board

When the remote controller cannot be found or when you dont want to change setting of the network address No. from the remote controller, use the setup switch SW01 on the network adapter P.C. board (Network address No. setup switch) to set the address No.

<Procedure>

(1)Turn off the power.

(2)Turn of the address No. setup switch SW01 to ON side. Accordingly the address No. set on the remote controller is invalidated. (See Fig. 2.)

(3)Set the network address No. with combination of ON and OFF of to of the address No. setup switch SW01. The relation between combination of ON/OFF and address No. is described in Table 2. The right figure (Fig. 3) shows an example of case that the address No. is set to 16.

When the network address No. has been changed, be sure to turn of power of the central control remote controller again or to reset the remote controller using the reset hole on the operation panel of the central control remote controller.

No. setup switch

ON

ON side OFF side

1 2 3 4 5 6 7 (Numeral side)

SW01

Address No. setup

Fig. 2

Setup example of address No. 16

ON

ON side OFF side (Numeral side)

1

2

3

4

5

6

7

Fig. 3

100

Page 100
Image 100
Toshiba RAV-SM560BT-E How to Set an Address Number, How to set from the remote controller at indoor unit side, 100

RAV-SM800BT-E, RAV-SM560BT-E, RAV-SM560AT-E, RAV-SM560UT-E, RAV-SM800UT-E specifications

Toshiba offers a range of innovative air conditioning units designed for optimal performance and efficiency, including the RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM560BT-E, and RAV-SM800BT-E models. Each of these units is part of Toshiba's commitment to quality air conditioning solutions that cater to both residential and commercial spaces.

The RAV-SM800UT-E and RAV-SM800AT-E models are notable for their impressive cooling and heating capacities, making them ideal for larger spaces. They feature advanced inverter technology, which adjusts the compressor's speed to maintain a consistent temperature while reducing energy consumption. This not only ensures comfort but also translates into significant energy savings over time.

In terms of design, these models benefit from Toshiba's sleek and modern aesthetics, allowing them to blend seamlessly into various interior styles. The noise levels are remarkably low, thanks to Toshiba's engineering, making these units suitable for use in environments where quiet operation is paramount, such as offices and bedrooms.

The RAV-SM560UT-E and RAV-SM560BT-E models offer similar performance but are tailored for smaller spaces without compromising on efficiency. They include features such as multilayer air filtration systems that effectively remove dust, allergens, and other pollutants, ensuring a healthier indoor air environment. Furthermore, they come equipped with intelligent control options, allowing users to operate the units remotely via smartphone applications.

Another standout characteristic of the RAV-SM800BT-E is its ability to provide both cooling and heating, making it a versatile option throughout the year. These units utilize R32 refrigerant, which has a lower global warming potential compared to traditional refrigerants, aligning with Toshiba's commitment to sustainability.

Each of these models is designed for easy installation and maintenance, featuring a user-friendly interface and robust build quality. The advanced diagnostics feature allows for timely troubleshooting and maintenance, ensuring the longevity of the units.

In summary, Toshiba's RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM560BT-E, and RAV-SM800BT-E models represent a blend of innovative technology, user-centric design, and environmental responsibility. These units not only deliver exceptional climate control but also contribute to reducing energy costs and improving indoor air quality, making them a smart choice for a wide range of applications.