Error mode detected by outdoor unit

: Flash, : Go on, : Go off

68

Wireless sensor

Wired remote

lamp display

controller

 

 

 

 

Operation

Timer

Ready

Check code

 

 

 

 

 

 

 

H01

 

 

 

 

 

 

 

 

H02

 

 

 

 

 

 

 

 

H03

 

 

 

 

 

 

 

 

L29

 

 

 

 

 

L31

 

 

 

 

 

 

 

 

P03

 

 

 

 

 

 

 

 

P04

 

 

 

 

 

 

 

 

P22

 

 

 

 

 

P26

 

 

 

 

 

P29

 

 

 

 

 

F04

 

 

 

 

 

F06

 

 

 

 

 

F08

 

 

 

 

 

Diagnostic function

Cause of operation

Breakdown of compressor

Displayed when error is detected

Compressor does not rotate.

Over-current protective circuit operates after specified time passed when compressor had been activated.

Current detection circuit error

Current value at AC side is high even during compressor-OFF.

Phase of power supply is missed.

Outdoor unit and other errors

Communication error between CDB and IPDU (Coming-off of connector)

Heat sink temperature error

(Detection of temperature over specified value)

Phase detection protective circuit operates. (Normal models)

Discharge temperature error

Discharge temperature over specified value was detected.

High-pressure protection error by TE sensor (Temperature over specified value was detected.)

Outdoor DC fan error

Inverter over-current protective circuit operates. (For a short time) Short voltage of main circuit operates.

IPDU position detection circuit error

Coming-off, disconnection or short of outdoor temperature sensor (TD)

Coming-off, disconnection or short of outdoor temperature sensor (TE/TS)

Coming-off, disconnection or short of outdoor temperature sensor (TO)

Status of air conditioner

Stop

Stop

Stop

Stop

Operation continues. (Compressor stops.)

Stop

Stop

Stop

Stop

Stop

Stop

Stop

Operation continues.

Condition

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Displayed when error is detected

Judgment and measures

1.Check power voltage. AC200V±20V

2.Overload operation of refrigerating cycle

3.Check current detection circuit at AC side.

1.Trouble of compressor (Compressor lock, etc.) : Replace compressor.

2.Defective cabling of compressor (Phase missing)

3.Phase-missing operation of power supply (3-phase model)

1.Compressor immediately stops even if restarted. : Check IPDU.

2.Phase-missing operation of power supply Check 3-phase power voltage and cables.

1.Check cables of CDB and IPDU.

2.Abnormal overload operation of refrigerating cycle

1.Check power phase order (Reversed phase)/phase missing.

2.Check outdoor P.C. board.

1.Check refrigerating cycle. (Gas leak)

2.Trouble of PMV

3.Check Td sensor.

1.Overload operation of refrigerating cycle

2.Check outdoor temperature sensor (TE).

3.Check outdoor CDB P.C. board.

1.Defective detection of position

2.Over-current protective circuit of outdoor fan driving unit operates.

3.Lock of outdoor fan

4.Check outdoor CDB P.C. board.

1.Inverter immediately stops even if restarted. : Compressor motor rare short

2.Check IPDU. : Cabling error

1.Position detection circuit operates even if operating compressor by removing 3P connector. : Replace IPDU.

1.Check outdoor temperature sensor (TD).

2.Check outdoor CDB P.C. board.

1.Check outdoor temperature sensor (TE/TS).

2.Check outdoor CDB P.C. board.

1.Check outdoor temperature sensor (TO).

2.Check outdoor CDB P.C. board.

For an error mode detected in outdoor unit, the fan operates because sub unit of a group operation does not communicate with the outdoor unit.

Page 68
Image 68
Toshiba RAV-SM560UT-E, RAV-SM800AT-E Error mode detected by outdoor unit, Diagnostic function Cause of operation

RAV-SM800BT-E, RAV-SM560BT-E, RAV-SM560AT-E, RAV-SM560UT-E, RAV-SM800UT-E specifications

Toshiba offers a range of innovative air conditioning units designed for optimal performance and efficiency, including the RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM560BT-E, and RAV-SM800BT-E models. Each of these units is part of Toshiba's commitment to quality air conditioning solutions that cater to both residential and commercial spaces.

The RAV-SM800UT-E and RAV-SM800AT-E models are notable for their impressive cooling and heating capacities, making them ideal for larger spaces. They feature advanced inverter technology, which adjusts the compressor's speed to maintain a consistent temperature while reducing energy consumption. This not only ensures comfort but also translates into significant energy savings over time.

In terms of design, these models benefit from Toshiba's sleek and modern aesthetics, allowing them to blend seamlessly into various interior styles. The noise levels are remarkably low, thanks to Toshiba's engineering, making these units suitable for use in environments where quiet operation is paramount, such as offices and bedrooms.

The RAV-SM560UT-E and RAV-SM560BT-E models offer similar performance but are tailored for smaller spaces without compromising on efficiency. They include features such as multilayer air filtration systems that effectively remove dust, allergens, and other pollutants, ensuring a healthier indoor air environment. Furthermore, they come equipped with intelligent control options, allowing users to operate the units remotely via smartphone applications.

Another standout characteristic of the RAV-SM800BT-E is its ability to provide both cooling and heating, making it a versatile option throughout the year. These units utilize R32 refrigerant, which has a lower global warming potential compared to traditional refrigerants, aligning with Toshiba's commitment to sustainability.

Each of these models is designed for easy installation and maintenance, featuring a user-friendly interface and robust build quality. The advanced diagnostics feature allows for timely troubleshooting and maintenance, ensuring the longevity of the units.

In summary, Toshiba's RAV-SM800UT-E, RAV-SM560UT-E, RAV-SM800AT-E, RAV-SM560BT-E, and RAV-SM800BT-E models represent a blend of innovative technology, user-centric design, and environmental responsibility. These units not only deliver exceptional climate control but also contribute to reducing energy costs and improving indoor air quality, making them a smart choice for a wide range of applications.