Toshiba RAV-SM800UT-E 55, Item, Outline of specifications, Remarks, Last push priority, Center

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 55
Image 55
– 55 –

No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

11

Filter sign display

1)

The operation time of the indoor fan is calculated, the filter

[FILTER] goes

 

 

 

lamp (Orange) on the display part of the main unit goes on

on.

 

 

 

when the specified time (240H) has passed. When a wired

 

 

 

 

remote controller is connected, the filter reset signal is sent to

 

 

 

 

the remote controller, and also it is displayed on LCD of the

 

 

 

 

wired remote controller.

 

 

 

2) When the filter reset signal has been received from the wired

 

 

 

 

remote controller after [FILTER] lamp has gone on or when

 

 

 

 

the filter check button (Temporary button) is pushed, time of

 

 

 

 

the calculation timer is cleared. In this case, the measurement

 

 

 

 

time is reset if the specified time has passed, and display on

 

 

 

 

LCD and the display on the main unit disappear.

 

 

 

 

 

 

12

Central control

1)

Setting at the central remote controller side enables to select the contents which

 

mode selection

 

can be operated on the remote controller at indoor unit side.

 

2)Operation contents on the remote controller at indoor unit side

[Last push priority] :

The operation contents can be selected from both remote controller and the central controller of the indoor unit side, and the operation is performed with the contents selected at the last.

[Center] :

Start/Stop operation only can be handled on the remote controller at indoor unit side.

[Operation Prohibited] :

It cannot be operated on the remote controller at indoor unit side. (Stop status is held.)

3)Display on the display part of the main unit or wired remote controller

Setup on central

Display on wired remote

Display on wired

Display on main unit

control remote

controller

remote controller

(Only in case of no wired remote

controller

(In case of RBC-AM1)

(In case of RBC-AM1)

controller)

Last push priority

[Central control] goes off.

[Center] goes off.

No display

 

 

 

 

Center

[Central control] goes on.

[Center] goes on.

[DEFROST] lamp (Orange) 1Hz flashes.

 

 

 

 

Operation prohibited

[Central control] flashes.

[Center] flashes.

[DEFROST] lamp (Orange) 5Hz flashes.

 

 

 

 

NOTE : When a wired remote controller is connected, there is no display on the main unit.

13

Energy-save

1) Selecting [AUTO] mode enables an energy-saving to be operated.

 

control

2)

The setup temperature is shifted (corrected) in the range not to lose the comfort

 

(By connected

 

 

ability according to input values of various sensors.

 

outdoor unit)

 

 

3)

Data (Input value room temp. Ta, Outside temp. To, Air volume, Indoor heat

 

 

 

 

 

exchanger sensor temp. Tc) for 20 minutes are taken the average to calculate

 

 

 

correction value of the setup temperature.

 

 

 

 

 

 

 

 

 

 

4)

The setup temperature is shifted every 20 minutes, and the shifted range is as

 

 

 

follows.

In cooling time : +1.5 to 1.0K

 

 

 

 

 

 

 

 

 

 

 

 

In heating time : 1.5 to +1.0K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Max. frequency

1) This control is operated by selecting

Ta( C)

Normal control

 

 

 

 

 

 

cut control

 

[AUTO] operation mode.

 

 

 

 

 

+4

 

 

 

2) COOL operation mode: the fre-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. frequency is restricted

 

 

 

quency is controlled according to the

+3

 

 

 

 

 

 

 

to approximately the rated

 

 

 

following figure if To < 28°C.

Tsc

 

 

cooling frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) HEAT operation mode: the frequency

Ta( C)

 

 

 

 

 

 

 

 

 

 

 

is controlled according to the right

 

 

 

 

 

 

 

 

 

 

 

Tsh

 

 

 

 

 

 

 

 

 

 

 

figure if To > 15°C.

 

 

Max. frequency is restricted

 

 

 

 

 

 

 

 

 

 

 

-3

 

 

to approximately the rated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heating frequency

 

 

 

 

 

-4

 

 

 

 

 

 

 

 

 

 

 

 

Normal control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

Page 55
Image 55
Toshiba RAV-SM800UT-E 55, Item, Outline of specifications, Remarks, Last push priority, Center, Operation Prohibited