Toshiba RAV-SM800UT-E, RAV-SM800AT-E, RAV-SM560UT-E 43, Item, Outline of specifications, Remarks

Models: RAV-SM800BT-E RAV-SM560BT-E RAV-SM560AT-E RAV-SM560UT-E RAV-SM800UT-E RAV-SM800AT-E

1 181
Download 181 pages 61.65 Kb
Page 43
Image 43
– 43 –

No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

9

Drain pump control

1)

In cooling operation (including Dry operation), the

 

 

(For the duct, when

 

drain pump is usually operated.

 

 

2)

If the float switch operates while drain pump

 

 

the drain-up kit

 

 

 

operates, the compressor stops, the drain pump

 

 

(sold separately) is

 

 

 

 

continues the operation, and a check code is

 

 

mounted)

 

 

 

 

output.

 

 

 

 

 

 

 

3)

If the float switch operates while drain pump stops,

 

 

 

 

the compressor stops and the drain pump oper-

 

 

 

 

ates. If the float switch keeps operating for approx.

 

 

 

 

4 minutes, a check code is output.

Check code [P10]

 

 

 

 

10

After-heat elimina-

When heating operation stops, the indoor fan operates

 

 

tion

with LOW mode for approx. 30 seconds.

 

 

 

 

 

 

11

Flap control

1)

Flap position setup

 

 

(For 4-way air

 

• When the flap position is changed, the position

 

 

 

moves necessarily to downward discharge

 

 

discharge cassette

 

 

 

 

position once to return to the set position.

 

 

type only)

 

 

 

 

• The flap position can be set up in the following

 

 

 

 

 

 

 

 

operation range.

 

 

 

 

In cooling/dry operation In heating/fan operation

 

In group twin/triple operation, the flap positions can be set up collectively or individually.

2)Swing setup

The swinging position can be moved in the following operation range.

All modes

• In group twin/triple operation, the swinging

 

positions can be set up collectively or individu-

 

ally.

Warning :

3) When the unit stops or when a warning is output,

A check code is displayed

the flap automatically moves downward.

on the remote controller,

4) While the heating operation is ready, the flap

and the indoor unit stops.

automatically moves upward.

(Excluding [F08] and

 

[L31])

– 43 –

Page 43
Image 43
Toshiba RAV-SM800UT-E, RAV-SM800AT-E, RAV-SM560UT-E, RAV-SM560AT-E service manual 43, Item, Outline of specifications, Remarks