Chapter 4 Input/output functions and wiring for typical applications

is established and then is no longer present, the controller generates a Generic AIP Failure diagnostic.

For the CO2 measurement configuration, a 4–20 mA sensor must be hard- wired to the AI4 terminal as shown in Figure 5. The sensor will transmit a 0–2000 ppm value to the BAS. This configuration has no direct effect on Tracer ZN521 operation. If a valid value is established and then is no longer present, the controller generates a CO2 Sensor Failure diagnostic.

Figure 5. AI4 terminal wiring: CO2 measurement

Tracer ZN521

24 Vac

CO2 sensor (Trane 5010 0828 shown)

24 Vac

GND Signal

For the RH measurement configuration, either a hard-wired 4–20 mA zone humidity sensor (see Figure 6) must provide a value to the controller or a BAS communicates a value to the controller. The controller uses this value to support the dehumidification function. (For more information, see “Dehumidification” on page 47.) If a valid hard-wired or communi- cated relative humidity value is established and then is no longer present, the controller generates a Humidity Input Failure diagnostic and disables the dehumidification function.

Figure 6. AI4 terminal wiring: RH measurement

Tracer ZN521

RH sensor

20