Chapter 5 Sequence of operations
Zone temperature control
The Tracer ZN521 zone controller uses two methods of zone temperature control:
•Cascade zone
•Simplified zone
Cascade zone control
Cascade zone control maintains zone temperature by controlling the dis- charge air temperature to control the zone temperature. The controller uses the difference between the measured zone temperature and the active zone temperature setpoint to produce a discharge air temperature setpoint. The controller compares the discharge air temperature setpoint with the discharge air temperature and calculates a unit heating/cooling capacity accordingly (see Figure 18). The end devices (outdoor air damper, valves, etc.) operate in sequence based on the unit heating/cooling capac- ity
Figure 18. Cascade zone control
Active zone |
|
temperature |
|
setpoint | Difference |
|
Calculated discharge air temperature setpoint
Difference
Calculated unit heating/cooling capacity
Measured
zone
temperature
Measured
discharge air temperature
If the discharge air temperature falls below the Discharge Air Control Point Low Limit (configurable using the Rover service tool) and cooling capacity is at a minimum, available heating capacity will be used to raise the discharge air temperature to the low limit (see “Discharge air temper- ing” on page 39).
Simplified zone control
In the unoccupied mode, the controller maintains the zone temperature by calculating the required heating or cooling capacity
38 |
|