Wiring requirements and options

Figure 13. Electric heat unit with DX cooling

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

GND 24V 24V 24V BI1

BI2

BI3

AC POWER

BINARY INPUTS

ZONE SENSOR

SERVICE

PIN LED ZN GND SET FAN GND AI1

24 V

Fan, high speed

24 VExhaust

24 V

DX cooling

24 V

Electric heat, stage 1 (optional)

24 V

Electric heat, stage 2 (optional)

 

24 V

 

Outdoor air damper actuator

 

24 V

Open Close

Generic/baseboard heat

 

BI4

1

2

3

4

5

6

7

8

9

10

STATUS

 

 

 

 

 

 

 

 

 

 

 

LED

BINARY OUTPUTS

ANALOG INPUTS

COMM5

 

 

COMM5

AI2

AI3 +20 AI4 GND A

B A B LED

On

Cancel

1

 

2

 

3

 

4

 

5 LonTalk

Entering water

6

temperature

Discharge air temperature

}

LonTalk

AI4 input: Seein Figures 5 and 6

on page 20 for

wiring options

out

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.