Chapter 1 Overview and specifications
Agency listing/compliance
UL and
UL
FCC Part 15, Class A
ASHRAE Cycle 1 & Cycle 2 control sequences
Additional components
The Tracer ZN521 zone controller requires the use of additional compo- nents for monitoring and proper control of the associated equipment. The use of specific components depends on the application. These components are not included with the Tracer ZN521 zone controller.
Power transformer
Use a
Water, duct, and outdoor-air temperature sensors
Temperature sensors must be Trane 10 kΩ (at 25°C) thermistors. Enter- ing water and discharge air inputs may use a sealed temperature sensor (part number 4190 1100).
Binary input switching devices
Occupancy, condensate overflow,
Output devices
Output devices connected to the Tracer ZN521 binary outputs cannot exceed 12 VA (0.5 A) current draw at 24 Vac.
Zone temperature sensors
Table 1 shows the Trane zone temperature sensors that are supported by the Tracer ZN521 zone controller.
Valve actuators
Valve actuators cannot exceed 12 VA draw at 24 Vac. For
4 |
|