Chapter 6 Status indicators for operation and communication

Table 11. Manual output test sequence for non-face-and-bypass configurations

Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9 BOP10

heat 2)Baseboard 1)Generic

close damper, air Outdoor

open damper, air Outdoor

2 stage heat, 2)Electric close valve, 1)Heating

1 stage heat, 3)Electric valve heat position-2)Two open valve, 1)Heating

close valve, Cooling/changeover

compressor 3)DX

valve changeover cooling/ position-2)Two

open valve, 1)Cooling/changeover

low Fan

2)Exhaust medium 1)Fan

high Fan

pressed is button Test times of Number

11: Exit5

The controller turns off all fan and electric heat outputs and drives all dampers and valves closed.

The controller attempts to clear all diagnostics.

If configured for a 3-speed fan, the medium fan speed output will energize at step 3. If configured for a 2-speed fan, the fan remains on high speed at step 3.

If configured for a 3-speed fan, the medium fan speed output energizes at step 4. If configured for a 2-speed fan, the low fan speed output energizes at step 4. If configured for a 1-speed fan, the fan remains on high speed at step 4.

If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The exhaust fan output is shared with medium fan speed.

After step 10, the manual output test performs an exit, which initiates a reset to restore the controller to normal operation.

1

2

3

4

5

6

54

CNT-SVX07C-EN

Page 64
Image 64
Trane N512, Zone Controller, CNT-SVX07C-EN manual Close damper, air Outdoor Open damper, air Outdoor