Chapter 4 Input/output functions and wiring for typical applications

Figure 8. Two-pipe hydronic-heating unit

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

24 V

Fan, high speed

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

 

24 V

 

 

Heating valve

 

 

24 V

 

 

Outdoor air damper actuator

 

 

24 V

Open Close

Open Close

Generic/baseboard heat

 

Entering water

LonTalk temperature

Discharge air temperature

 

LonTalk

AI4 input: See

in

Figures 5 and 6

on page 20 for

 

wiring options

out

 

Outdoor air or generic temperature

 

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) termi-

24

CNT-SVX07C-EN

Page 34
Image 34