Chapter 5 Sequence of operations

Two-position control of a modulating outdoor air damper

The Tracer ZN521 does not support a two-position outdoor air damper actuator. However, a modulating outdoor/return air damper actuator can be used for two-position control. Two-position control can be accomplished by not providing an outdoor air temperature (neither hard-wired nor com- municated) to the controller, and by setting the damper minimum posi- tion (using the Rover service tool) to the desired value (typically, 100%).

Face-and-bypass damper operation

The Tracer ZN521 can control a face-and-bypass damper to modulate a percentage of air to the face of the coil(s) and around (bypass) the coil(s) to maintain zone comfort. For two-pipe changeover applications, if the con- troller requests heating and hot water is available, the face-and-bypass damper modulates to the face position. If the controller requests heating and hot water is not available, the face-and-bypass damper remains in the bypass position, and water sampling may be initiated (see “Entering water temperature sampling function” on page 40). For four-pipe changeover applications, both heat and cool capacity are assumed to be available.

Face-and-bypass, isolation-valve operation

ATracer ZN521 with a face-and-bypass damper controls on/off isolation valve(s) to prevent unwanted water flow through the coil(s) when no air- flow is passing over the coil (100% bypass). In two-pipe applications, the isolation valve stops water flow, preventing radiant heat (heating mode) and excessive condensate (cooling mode) from the coil. In four-pipe appli- cations, the isolation valves are used to prevent simultaneous heating and cooling.

The heating or cooling isolation valve opens whenever capacity is requested (>0%) as the face-and-bypass damper begins to modulate toward the coil face. The isolation valve closes when capacity returns to 0%.

DX cooling operation

The Tracer ZN521 supports one stage of direct expansion (DX) compres- sor operation for cooling only.

Note:

The controller does not use the DX compressor and economizing simultaneously. Not doing so prevents short cycling from occur- ring if the entering air temperature is too low for the evapora- tor coil to operate as designed.

46

CNT-SVX07C-EN

Page 56