Manual output test

Table 12. Manual output test sequence for face-and-bypass configurations (two-position isolation valves only)

Step

Result

BOP1

BOP2

BOP3

BOP4

BOP5

BOP6

BOP7

BOP8

BOP9

BO

Number of times Test button is pressed

 

Fan high

1)Fan medium 2)Exhaust fan

Fan low

Two-position cool/ changeover valve

Face and bypass damper, open to face

Two-position heat valve

Face and bypass damper, close (bypass)

Outdoor air damper, open

Outdoor air damper, close

1)Generic

 

 

 

 

 

 

 

 

 

 

 

 

1

Begins test

Off

Off

Off

Off

Off

Off

On/Close

Off

On/Close

Off

 

mode1

 

 

 

 

 

 

 

 

 

 

2

Fan high2

On/High

Off

Off

Off

On/Open

Off

Off

Off

Off

Off

3

Fan

Off

1) On/Med

Off

Off

On/Open

Off

Off

Off

Off

Off

 

medium3

 

2) Off

 

 

 

 

 

 

 

 

4

Fan low4

Off

Off

On/Low

Off

On/Open

Off

Off

Off

Off

Off

5

Main open,

On/High

Off

Off

On/Open

On/Open

Off

Off

Off

Off

Off

 

DX on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Main close,

On/High

Off

Off

Off

On/Open

On/Open

Off

Off

Off

Off

 

DX off, aux

 

 

 

 

 

 

 

 

 

 

 

open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Aux open,

On/High

1) Off

Off

Off

On/Open

On/Open

Off

Off

Off

Off

 

EH1 on,

 

2) On

 

 

 

 

 

 

 

 

 

exhaust

 

 

 

 

 

 

 

 

 

 

 

fan5

 

 

 

 

 

 

 

 

 

 

8

Aux close,

On/High

Off

Off

Off

Off

Off

On/Close

On/Open

Off

Off

 

damper

 

 

 

 

 

 

 

 

 

 

 

open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Outdoor air

On/High

Off

Off

Off

Off

Off

On/Close

Off

On/Close

Off

 

damper

 

 

 

 

 

 

 

 

 

 

 

close

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Generic/

On/High

Off

Off

Off

Off

Off

On/Close

Off

Off

On

 

baseboard

 

 

 

 

 

 

 

 

 

 

 

heat

 

 

 

 

 

 

 

 

 

 

 

energized6

 

 

 

 

 

 

 

 

 

 

11: Exit5

 

 

 

 

 

 

 

 

 

 

 

1The controller turns off all fan and electric heat outputs and drives all dampers and valves closed.

2The controller attempts to clear all diagnostics.

3If configured for a 3-speed fan, the medium fan speed output will energize at step 3. If configured for a 2-speed fan, the fan remains on high at step 3.

4If configured for a 3-speed fan, the medium fan speed output energizes at step 4. If configured for a 2-speed fan, the low fan speed output en at step 4. If configured for a 1-speed fan, the fan remains on high speed at step 4.

5If the unit is configured for a 1- or 2-speed fan, the exhaust fan output energizes on step 7. The exhaust fan output is shared with medium fan

6After step 10, the manual output test performs an exit, which initiates a reset to restore the controller to normal operation.

CNT-SVX07C-EN

55

Page 65
Image 65
Trane CNT-SVX07C-EN, Zone Controller, N512 manual Step Result, BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9