Diagnostics

Smart reset diagnostics

After the controller detects the first smart reset diagnostic, the unit waits 30 minutes before initiating the smart reset function. If another diagnos- tic of this type occurs again within 24 hours after an automatic clearing, you must clear the diagnostic manually by using any of the ways shown for “Manual (latching) diagnostics.”

Informational diagnostics

Informational diagnostics provide information about the status of the controller. They do not affect machine operation. They can be cleared from the controller using any of the ways shown for “Manual (latching) diag- nostics.”

Table of diagnostics

Table 16 The tables present each diagnostic that can be generated by the

Tracer ZN521, its effect on outputs (consequences), and its type.

Note:

The generic binary output is unaffected by diagnostics.

Table 16. Diagnostics

Diagnostic

Probable cause

Consequences

Diagnostic

type

 

 

 

 

 

 

 

Maintenance Required

Fan run hours exceed the

Fan unaffected

Informational

 

time set to indicate filter

Valves unaffected

 

 

change

Electric heat unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

 

 

Condensate Overflow

The drain pan is full of

Fan off

Manual

 

water

Valves closed

 

 

 

Outdoor air damper closed

 

 

 

Face and bypass damper bypass

 

 

 

DX/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

Low Coil Temp Detection

The leaving fluid temper-

Fan off

Smart reset/

 

ature may be close to

Valves open

Manual

 

freezing

Outdoor air damper closed

 

 

 

Face and bypass damper bypass

 

 

 

DX/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

Low Airflow—Fan Failure

The fan drive belt, con-

Fan off

Manual

 

tactor, or motor has

Valves closed

 

 

failed.

Outdoor air damper closed

 

 

 

Face and bypass damper bypass

 

 

 

DX/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

CNT-SVX07C-EN

59

Page 69
Image 69