Binary outputs

Binary outputs

The ZN521 zone controller supports fan coil, blower coil, and unit ventila- tor applications that may include the following components:

Supply fan with up to three speeds

Hydronic cooling and/or heating coils with two-position or tri-state modulating control valve

DX cooling (single stage)

Electric heat (single stage or two stage)

Baseboard heat (single stage)

Tri-state modulating outdoor/return air damper

Tri-state modulating face-and-bypass damper

The Tracer ZN521 controller includes ten binary outputs. Each binary output is a triac with a rating of 12 VA at 24 Vac. Table 6 describes the function of each output.

Table 6: Binary output functions

Binary output

Functions

 

 

1

• Fan high

 

 

2

• Fan medium

 

• Exhaust fan or damper

 

 

3

• Fan low

 

 

4

• Modulating cooling/changeover valve, open

 

Two-position cooling/changeover valve

 

• DX cooling

 

 

5

• Modulating cooling/changeover valve, close

 

Face-and-bypass damper, open to face

 

 

6

• Modulating heating valve, open

 

Two-position heating valve

 

• Electric heat, stage 1

 

 

7

• Modulating heating valve, close

 

Face-and-bypass damper, close (bypass)

 

• Electric heat, stage 2

 

 

8

• Outdoor air damper, open (return air damper, close)

 

 

9

• Outdoor air damper, close (return air damper, open)

 

 

10

• Baseboard heat

 

• Generic

 

 

Generic binary output

Binary output 10 is the only output that can be configured as a generic binary output. When configured as a generic binary output, it can be con- trolled only by a BAS, and has no direct effect on Tracer ZN521 operation.