Chapter 7 Troubleshooting
Table 17. Fan does not energize (Continued)
Probable cause | Explanation |
|
|
Cycling fan operation/ | The controller operates the fan continuously when in the occupied, occupied standby, or |
continuous | occupied bypass mode. When the controller is in the unoccupied mode, the fan is cycled |
| between high speed and off with capacity. |
|
|
Unoccupied operation | Even if the controller is configured for continuous fan operation, the fan normally cycles |
| with capacity during unoccupied mode. While unoccupied, the fan cycles on or off with |
| heating/cooling to provide varying amounts of heating or cooling to the space. |
|
|
Fan mode off | If a local fan mode switch determines the fan operation, the off position controls the fan |
| off. |
|
|
Requested mode off | You can communicate a desired operating mode (such as off, heat, and cool) to the con- |
| troller. If off is communicated to the controller, the unit controls the fan off. There is no |
| heating or cooling. |
|
|
Table 18. Valves remain closed
Probable cause | Explanation |
|
|
Unit wiring | The wiring between the controller outputs and the valve(s) must be present and correct |
| for normal valve operation. Refer to applicable wiring diagram. |
|
|
Failed end device | The valves must be checked to ensure proper operation. |
|
|
No power to the con- | If the controller does not have power, the unit valve(s) will not operate. For the Tracer |
troller | ZN521 controller to operate normally, you must apply an input voltage of 24 Vac. If the |
| green LED is off continuously, the controller does not have sufficient power or has failed. |
|
|
If | |
| two conditions occurs: |
| 1) The controller exits |
| 2) The controller exits |
|
|
Diagnostic present | Several diagnostics affect valve operation. For information about these diagnostics, see |
| Table 16 on page 59. |
|
|
Normal operation | The controller opens and closes the valves to meet the unit capacity requirements. |
|
|
Unit configuration | The controller must be properly configured based on the actual installed end devices and |
| application. If the unit configuration does not match the actual end device, the valves |
| may not work correctly. |
|
|
Manual output test | The controller includes a manual output test sequence you can use to verify output oper- |
| ation and associated output wiring. However, based on the current step in the test |
| sequence, the valves may not be open. Refer to the “Manual output test” on page 52. |
|
|
Random start | After |
observed | controller remains off until the random start time expires. |
|
|
Requested mode off | You can communicate a desired operating mode (such as off, heat, and cool) to the con- |
| troller. If off is communicated to the controller, the unit controls the fan off. There is no |
| heating or cooling. |
|
|
Entering water | The controller includes entering water temperature sampling logic, which is automati- |
temperature | cally initiated during |
sampling logic | either too cool or too hot for the desired heating or cooling. (See “AI1: Entering water |
| temperature” on page 17.) |
|
|
Valve configuration | Make sure the valves are correctly configured, using the Rover service tool, as normally |
| open or normally closed as dictated by the application. |
|
|
64 |
|