Additional components

Table 1. Tracer zone temperature sensor options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timed

 

 

 

 

 

Fan

 

 

 

Zone

 

override

 

BAS

 

 

 

 

 

 

 

 

 

buttons

Comm

 

 

 

 

 

 

 

 

 

 

 

order

Use

 

 

 

 

 

 

 

 

 

 

number

 

 

 

 

 

 

Setpoint

 

 

 

 

jack

 

 

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

Med

Low

Auto

Off

thumb-

On

 

Cancel

 

 

 

sensor

 

 

 

 

 

 

 

 

 

wheel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1087

Any

 

 

 

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1088

Any

 

 

 

 

 

 

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1090

Any

 

 

 

 

 

x

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1094

Any

 

 

 

 

 

x

x

 

 

 

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1095

Unit

x

 

x

 

x

x

x

x

 

x

x

 

ventilator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1115

Fan coil

x

x

x

x

x

x

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1116

Unit

x

 

x

x

x

x

x

x

 

x

x

 

ventilator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4190 1117

Any

 

 

 

x

x

x

x

x

 

x

x

 

 

 

 

 

 

 

 

 

 

 

 

 

returns the valve to normally open or closed (dependent on the desired default position). For modulating valve control, use tri-state modulating actuators with or without a spring return, as required by the application.

Damper actuators

Damper actuators cannot exceed 12 VA draw at 24 Vac. For control of out- door/return air dampers, use tri-state modulating actuators that incorpo- rate a spring return.

Zone humidity sensor

For measurement of relative humidity (RH), the Tracer ZN521 requires a zone humidity sensor with a 4–20 mA output, where 4 mA is 0% RH and 20 mA is 100% RH. The controller provides 20 Vdc to power the zone humidity sensor.

CO2 sensor

For CO2 measurement, the Tracer ZN521 requires a CO2 sensor with a 4– 20 mA output, where 4 mA = 0 ppm and 20 mA = 2000 ppm.

CNT-SVX07C-EN

5

Page 15
Image 15
Trane Zone Controller, N512 Damper actuators, Zone humidity sensor, CO2 sensor, Tracer zone temperature sensor options