Discharge air tempering
Discharge air tempering
If the controller is in cooling mode, cascade zone control initiates a dis- charge air tempering function when the discharge air temperature falls below the Discharge Air Control Point Low Limit (configurable using the Rover service tool) and all cooling capacity is at a minimum. The dis- charge air tempering function allows the controller to provide heating capacity (if available) to raise the discharge air temperature to the Dis- charge Air Control Point Low Limit.
The discharge air tempering function is often initiated under the follow- ing circumstances: Cold outdoor air is brought in through the outdoor air damper when the damper is at (a high) minimum position, causing the discharge air temperature to fall below the Discharge Air Control Point Low Limit.
Morning warm-up
The morning
Morning cool-down
The morning
Heating or cooling mode
The heating or cooling mode can be determined in one of two ways:
•By a communicated signal from a BAS or a peer controller
•Automatically, as determined by the controller
A communicated heating signal permits the controller to heat only. A communicated cooling signal permits the controller to cool only. A com- municated auto signal allows the controller to automatically change from heating to cooling and vice versa.
| 39 |