Chapter 6 Status indicators for operation and communication

Diagnostics

Diagnostics are informational messages that indicate the operational sta- tus of the controller. In response to most diagnostics, the controller attempts to protect the equipment by enabling or disabling, or opening or closing, specific outputs. Other diagnostics provide information about the status of the controller, but have no effect on outputs. Diagnostics are reported in the order in which they occur. Multiple diagnostics can be present simultaneously. Diagnostic messages are viewed using the Rover service tool or through a BAS.

Types of diagnostics

Diagnostics are categorized according to the type of clearing method each uses and the type of information each provides.

The four categories are:

Manual (latching)

Automatic (nonlatching)

Smart reset

Informational

Note:

Clearing diagnostics refers to deleting diagnostics from the software; it does not affect the problem that generated the mes- sage. For help with diagnosing a problem, see Chapter 7, “Trou- bleshooting”.

Manual (latching) diagnostics

Manual diagnostics (also referred to as latching) cause the unit to shut down. Manual diagnostics can be cleared from the controller in one of the following ways:

By using the Rover service tool (see “Resetting a diagnostic” in EMTX-SVX01A-EN, Rover Installation/Operation/and Program- ming guide).

Through a building automation system (see product literature)

By initiating a manual output test at the controller (see “Manual out- put test” on page 52)

By cycling power to the controller. When the 24 Vac power to the con- troller is cycled off and then on again, a power-up sequence occurs.

By turning the zone sensor fan switch to OFF and then back to any other setting. (This feature will be available beginning with controller software version 2.10.)

Automatic (nonlatching) diagnostics

Automatic diagnostics clear automatically when the problem that gener- ated the diagnostic is solved.

58

CNT-SVX07C-EN

Page 68
Image 68
Trane CNT-SVX07C-EN, Zone Controller, N512 manual Diagnostics, Types of diagnostics