Trane CNT-SVX07C-EN, Zone Controller, N512 manual Damper unaffected

Models: Zone Controller CNT-SVX07C-EN N512

1 84
Download 84 pages 12.01 Kb
Page 71
Image 71

 

 

 

Diagnostics

Table 16. Diagnostics (Continued)

 

 

 

 

 

 

Diagnostic

Probable cause

Consequences

Diagnostic

type

 

 

 

 

 

 

 

Generic AIP Failure

Invalid or missing value

Fan unaffected

Informational

 

for generic analog input

Valves unaffected

 

 

 

Outdoor air damper unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

 

 

Local Fan Mode Failure

Invalid or missing fan-

Fan unaffected

Automatic

 

speed switch (reverts to

Valves unaffected

 

 

default fan speed)

Outdoor air damper unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

 

 

Local Setpoint Failure

Invalid or missing value

Fan unaffected

Automatic

 

for zone temperature set-

Valves unaffected

 

 

point (reverts to default

Outdoor air damper unaffected

 

 

setpoint)

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

 

 

Generic Temperature Failure

Invalid or missing

Fan unaffected

Informational

 

generic temperature

Valves unaffected

 

 

value

Outdoor air damper unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

 

 

Invalid Unit Configuration

Software is configured

Fan off

Manual

 

improperly

Valves off

 

 

 

Outdoor air damper closed

 

 

 

Face and bypass damper closed

 

 

 

DX cooling/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

Normal

On start-up

Fan unaffected

Automatic

 

 

Valves unaffected

 

 

 

Electric heat unaffected

 

 

 

Compressors unaffected

 

 

 

Damper unaffected

 

 

 

 

 

CNT-SVX07C-EN

61

Page 71
Image 71
Trane CNT-SVX07C-EN, Zone Controller, N512 manual Damper unaffected