Chapter 3

Mounting the controller

This chapter gives recommendations and requirements for mounting a Tracer ZN521 zone controller.

Location recommendations

Trane recommends locating the Tracer ZN521 zone controller:

Near the controlled piece of equipment to reduce wiring costs

Where it is easily accessible for service personnel

Where public access is restricted to minimize the possibility of tam- pering or vandalism

The controller can often be mounted inside the wiring enclosure of the associated mechanical equipment.

Operating environment requirements

Operate a Tracer ZN521 zone controller in an indoor environment that meets the following requirements:

Temperature: from 32°F to 140°F (from 0°C to 60°C)

Relative humidity: 5–95%, noncondensing

CNT-SVX07C-EN

11