Chapter 4 Input/output functions and wiring for typical applications

Figure 12. Two-pipe heating unit with DX cooling

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

24 V

Fan, high speed

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

24 V

DX cooling

 

24 V

 

 

Heating valve

 

 

24 V

 

 

Outdoor air damper actuator

Open Close

Open Close

24 V

Generic/baseboard heat

 

 

GND 24V 24V 24V BI1

BI2

BI3

BI4

1 2 3 4 5 6 7 8 9 10 STATUS

 

 

 

 

LED

AC POWER

BINARY INPUTS

 

BINARY OUTPUTS

ZONE SENSOR

ANALOG INPUTS

COMM5

 

SERVICE

 

 

 

COMM5

PIN LED ZN GND SET FAN GND AI1

AI2

AI3 +20 AI4 GND A

B A B

LED

On

Cancel

1

 

2

 

3

 

4

 

5 LonTalk

Entering water

6

temperature

Discharge air temperature

}

LonTalk

AI4 input: See

in

Figures 5 and 6

 

on page 20 for

 

wiring options

out

 

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.

28

CNT-SVX07C-EN

Page 38
Image 38
Trane CNT-SVX07C-EN, Zone Controller, N512 manual Two-pipe heating unit with DX cooling