Trane CNT-SVX07C-EN, Zone Controller Two-pipe hydronic heating/cooling unit with auto changeover

Models: Zone Controller CNT-SVX07C-EN N512

1 84
Download 84 pages 12.01 Kb
Page 35
Image 35

Wiring requirements and options

Figure 9. Two-pipe hydronic heating/cooling unit with auto changeover

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

24 V

Fan, high speed

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

24 V

Heating/cooling changeover valve

24 V

Electric heat, stage 1 (optional)

 

24 V

 

 

Electric heat, stage 2 (optional)

 

 

24 V

 

 

Outdoor air damper actuator

Open Close

Open Close

24 V

Generic/baseboard heat

 

 

Entering water

LonTalk temperature

Discharge air temperature

AI4 input: See

LonTalk

in

Figures 5 and 6

 

on page 20 for

 

wiring options

out

 

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.

CNT-SVX07C-EN

25

Page 35
Image 35
Trane CNT-SVX07C-EN, Zone Controller, N512 manual Two-pipe hydronic heating/cooling unit with auto changeover