Chapter 6 Status indicators for operation and communication

Table 16. Diagnostics (Continued)

Diagnostic

Probable cause

Consequences

Diagnostic

type

 

 

 

 

 

 

 

Space Temperature Failure

Invalid or missing value

Fan off

Automatic

 

for zone temperature

Valves closed

 

 

 

Outdoor air damper closed

 

 

 

Face and bypass damper bypass

 

 

 

DX/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

Entering Water Temp Failure

Invalid or missing value

Fan unaffected (enabled)

Automatic

 

for zone temperature

Valves unaffected

 

 

 

Outdoor air damper unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

DX/electric heat unaffected

 

 

 

Baseboard heat off

 

 

 

 

 

Discharge Air Temp Limit

Discharge air tempera-

Fan off

Automatic

 

ture has fallen below the

Valves open

 

 

Discharge Air Tempera-

Outdoor air damper closed

 

 

ture Low Limit

Face and bypass damper bypass

 

 

 

DX/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

Discharge Air Temp Failure

Invalid or missing value

Fan off

Automatic

 

for discharge air temper-

Valves closed

 

 

ature

Outdoor air damper closed

 

 

 

Face and bypass damper bypass

 

 

 

DX cooling/electric heat off

 

 

 

Baseboard heat off

 

 

 

 

 

Outdoor Air Temp Failure

Invalid or missing value

Fan unaffected

Automatic

 

for outdoor air tempera-

Valved unaffected

 

 

ture

Outdoor air damper minimum

 

 

 

position

 

 

 

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

 

 

Humidity Input Failure

Invalid or missing value

Fan unaffected

Automatic

 

for relative humidity

Valves unaffected

 

 

 

Outdoor air damper unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

Dehumidification sequence off

 

 

 

 

 

CO2 Sensor Failure

Invalid or missing value

Fan unaffected

Informational

 

for CO2

Valves unaffected

 

 

 

Outdoor air damper unaffected

 

 

 

Face and bypass damper unaffected

 

 

 

DX cooling/electric heat unaffected

 

 

 

Baseboard heat unaffected

 

 

 

 

 

60

CNT-SVX07C-EN

Page 70
Image 70
Trane N512, Zone Controller, CNT-SVX07C-EN manual Valved unaffected, Position