Chapter 4 Input/output functions and wiring for typical applications

Figure 10. Four-pipe hydronic heating/cooling unit

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (open=normal)*

24 Vac H N

24 V

Fan, high speed

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

24 VCooling valve

 

 

24 V

 

 

 

Heating valve

 

 

 

24 V

 

 

 

Outdoor air damper actuator

Open Close

Open Close

Open Close

24 V

Generic/baseboard heat

 

 

 

Entering water LonTalk temperature

Discharge air temperature

AI4 input: See

LonTalk

in

Figures 5 and 6

 

on page 20 for

 

wiring options

out

 

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.

26

CNT-SVX07C-EN