Troubleshooting

Table 22. Outdoor air damper remains open (Continued)

Probable cause

Explanation

 

 

Normal

The controller opens and closes the outdoor air damper based on the controller’s occu-

operation

pancy mode and fan status. Normally, the outdoor air damper is open during occupied

 

mode when the fan is running and closed during unoccupied mode. (See “Modulating

 

outdoor/return air dampers” on page 43.

 

 

Unit

The controller must be properly configured based on the actual installed end devices and

configuration

application. If the unit configuration does not match the actual end device, the outdoor air

 

damper may not work correctly.

 

 

Manual output test

The controller includes a manual output test sequence you can use to verify output oper-

 

ation and associated output wiring. However, based on the current step in the test

 

sequence, the outdoor air damper may be open. Refer to the “Manual output test” on

 

page 52.

 

 