Trane N512, Zone Controller manual Four-pipe heating/cooling unit with face-and-bypass damper

Models: Zone Controller CNT-SVX07C-EN N512

1 84
Download 84 pages 12.01 Kb
Page 43
Image 43

Wiring requirements and options

Figure 17. Four-pipe heating/cooling unit with face-and-bypass damper

24 VFan, high speed

Fan status (closed=on)*

Occupancy (open=occupied)*

Condensate overflow (closed=normal)*

Low-coil-temperature detection (closed=normal)*

24 Vac H N

24 V

Exhaust (or fan, medium speed)

24 V

Fan, low speed

24 V

Cooling isolation valve, open/close

24 V

Face and bypass damper actuator

24 V

Heating isolation valve, open/close 24 V

Outdoor air damper actuator

Open

Close

Open Close

24 V

Generic/baseboard heat

 

 

 

Entering water

LonTalk temperature

Discharge air temperature

LonTalk

AI4 input: See

in

Figures 5 and 6 on page 20 for

wiring options

out

Outdoor air or generic temperature

* All binary inputs are configurable.

Connect 24 V to an AC POWER (24V) terminal.

CNT-SVX07C-EN

33

Page 43
Image 43
Trane N512, Zone Controller, CNT-SVX07C-EN manual Four-pipe heating/cooling unit with face-and-bypass damper