Chapter 5 Sequence of operations
A
Table 9. Modulating outdoor air damper position setpoint determination
Occupancy | Fan speed | Active minimum setpoint | ||
setpoint | ||||
|
|
| ||
|
|
|
| |
Unoccupied | Any value | Any value | 0% (closed) | |
|
|
|
| |
Occupied | Valid | Any value | ||
Occupied bypass |
|
|
| |
Occupied standby |
|
|
| |
|
|
|
| |
Occupied | Invalid | Low | Occupied low fan minimum | |
Occupied bypass |
|
|
| |
Occupied standby |
|
|
| |
|
|
|
| |
Occupied | Invalid | Medium/high | Occupied minimum | |
Occupied bypass |
|
|
| |
|
|
|
| |
Occupied standby | Invalid | Medium/high | Occupied standby minimum | |
|
|
|
|
Table 10. Relationship between outdoor temperature sensors and damper position
| Modulating outdoor air damper position | ||||
Outdoor air temperature | Occupied or occupied |
| Occupied standby |
| Unoccupied |
|
| ||||
|
|
| |||
| bypass |
|
| ||
|
|
|
|
| |
|
|
|
|
|
|
No or invalid outdoor air | Open to occupied |
| Open to occupied standby |
| Closed |
temperature | minimum position |
| minimum position |
|
|
|
|
|
|
|
|
Failed outdoor air sensor | Open to occupied |
| Open to occupied standby |
| Closed |
| minimum position |
| minimum position |
|
|
|
|
|
|
|
|
Outdoor air temperature | Economizing; damper |
| Economizing; damper |
| Open and economizing |
present and economizing | controlled between |
| controlled between |
| during unit operation; oth- |
possible1 | occupied minimum |
| occupied standby |
| erwise closed |
| position and 100% |
| minimum position and |
|
|
|
|
| 100% |
|
|
|
|
|
|
|
|
Outdoor air temperature | Open to occupied mini- |
| Open to occupied standby |
| Closed |
present and economizing | mum position |
| minimum position |
|
|
not possible1 |
|
|
|
|
|
1For an explanation of the economizing feature, see “Economizing (free cooling)” on page 45.
44 |
|